1. Small air insulation gap: Due to some high-voltage switchgear manufacturers not strictly implementing the relevant technical standards of the switchgear, the air insulation gap between the phase and phase, as well as between the phase and ground of the charged bodies in some operating 10kV high-voltage switchgear cabinets is mostly between 100-125mm. As a pure air insulated electrical equipment, the "Technical Regulations for Design of High Voltage Distribution Equipment" clearly stipulate that the * * * small gap of pure air insulation in 10kV system is 125mm. Based on the results of AC withstand voltage test and accident analysis, it can be seen that the * * * small air insulation gap between phases and phases, and between phases and ground of the charged body in the 10kV high-voltage switchgear cabinet is less than 125mm, which is prone to accidents.