Flame retardant cable model ZC-YJV-0.6/1KV
Production execution standards: GB/T12706.1-2002~GB/T12706.3-2002 "Extruded Insulated Power Cables with Rated Voltage from 1kV (Um=1.2 kV) to 35kV (Um=40.5 kV)". Production can also be carried out according to user needs using the IEC 60502-1997 standard of the Electrical Commission.
1. The allowable long-term high operating temperature for cable conductors is 90 ℃.
2. During a short circuit (lasting no more than 5 seconds), the high temperature of the cable conductor shall not exceed 250 ℃.
3. The ambient temperature during cable laying shall not be lower than 0 ℃.
4. The small bending radius of a three core cable shall not be less than 15 times the outer diameter of the cable; Single core cables shall not be less than 20 times the outer diameter of the cable.