Solution for temperature transmitter output accuracy not meeting requirements
Date: 2022-10-11Read: 4
1Temperature TransmitterIs the power supply normal
If it is less than 12VDC, check if there is a large load in the circuit, and the input impedance of the transmitter load should comply with RL ≤ (transmitter supply voltage -12V)/(0.02A) Ω
2. Has integrated debugging been conducted
Perform integrated debugging
3. Does the insulation between the thermistor (or thermocouple) and the casing meet the requirements
If the insulation does not meet the requirements, corresponding insulation treatment is required.