Fault phenomenon - output is 0mA
1) The output transistor is damaged;
2) The output of the integrated operational amplifier is negative potential;
3) The bridge power supply is damaged or its circuit connection is open circuit;
4) Output transistor emitter resistance or open circuit lead;
5) The output connection is open.
Fault phenomenon - output is 10mA
1) Output transistor breakdown;
2) The integrated operational amplifier outputs a positive potential to make the transistor conductive;
3) The integrated operational amplifier is damaged.
Fault phenomenon - unstable output of digital display controller troubleshooting
1) Excessive external interference;
2) Unstable bridge power supply;
3) There are virtual solder joints in the relevant components or solder joints;
4) Poor contact of connectors;
5) The internal noise of the integrated operational amplifier increases;
6) The power supply voltage is too low;
7) The output transistor has poor characteristics.
Fault phenomenon - the monitor does not light up at all
1) Damaged power transformer or open circuit in related wiring;
2) The fuse is blown (open circuit);
3) The power connection of the digital panel meter is open circuit;
4) The LED display is damaged.
Fault phenomenon - display overflow
1) The input signal line has an open circuit in the inner part of the table;
2) The amplifier power supply is damaged;
3) The integrated operational amplifier is damaged;
4) 7107 is damaged;
5) The input of the digital panel table is open circuit.
Fault phenomenon - only displaying "000"
1) The bridge power supply of the signal conversion section is damaged;
2) The amplifier power supply is damaged;
3) 7107 is damaged;
4) The integrated operational amplifier is damaged.
Fault phenomenon - incomplete display text
1) The LED display is damaged;
2) 7107 is damaged;
3) There is an open circuit connecting the LED and 7107.