Compensation cable for thermocoupleThe usage characteristics are as follows:
1. Maximum operating temperature of conductor: Heat resistance grade: Perfluoroethylene propylene (F46) 200 ℃
Soluble polytetrafluoroethylene 260 ℃
Silicone rubber at 180 ℃
Ordinary grade: polyvinyl chloride at 70 ℃ and 105 ℃, cross-linked polyethylene at 90 ℃
Low smoke halogen-free flame-retardant polyolefin at 70 ℃, cross-linked at 90 ℃ and 125 ℃
2. Low ambient temperature: PVC sheath: fixed installation -40 ℃, non fixed installation -15 ℃
Fluoroplastic insulation and sheath: fixed installation -60 ℃, non fixed installation -20 ℃
3. Allowable bending radius for cables: The minimum allowable bending radius for non armored cables is 6 times the outer diameter
Copper tape shielded or steel tape armored point cables shall have a minimum diameter of 12 times the outer diameter of the cable
Fluoroplastic insulation and sheath with a minimum of 10 times the outer diameter of the cable