1、 Overview:

The intelligent wireless system is based on a dual serial communication multi-channel acquisition and control module, with4Road isolation input analog signal,8The road displays analog signals,10Group relay control output, Z can be equipped with multiple3Group analog control output. passCOM2The communication serial port is assigned to the on-site display touch screen,COM1The serial port is transmitted wirelessly through a transceiver. The wireless receiver pairing between the receiver and the industrial computer can be done againPCForm a measurement and control system on the computer for remote control. This system can be combined according to user requirements. It can carry out project measurement and control transformation in the chemical, pharmaceutical, power, environmental protection, agriculture, steel, and automotive industries.

2、 Main technical indicators:

1Input signal:8road4-20Ma(Connected to the weighing transmitter module).

2Input signal:16road4-20Ma(Connect temperature, pressure, feedback signals, etc.).

2Control output:6Road analog quantity4-20Ma,20Road switch quantity10A/220VSwitching quantity.

3Wireless433MHzfrequency modulation,visual range1000Rice.

47Inch touchscreen display.

5Module power supply:DC24V.(Linear power supply) Anti frequency converter interference

6Module size:300(Long)*110(Width)*60mm(high)*2(one)

7Overall power supply:AC220V

8Control cabinet size:1200mm(high)*600mm(Width)*400mm(shen

3、 Module terminal wiring diagram:

13Group analog output: output1 4-20Ma(68+,67-). Output2 4-20Ma(66+,65-). Output3 4-20Ma(64+,63-)

2Communication interface:37(A),38(B)RS485Connect to the computer port,41(A),42(B)RS485Connect to the touch screen port.

34High precision group weighing4-20mAInput.

48group4-20mAAnalog input,09to16yes5to12channel4-20mAAnalog input+17to20Analog input common negative.

510Output of group relay switch quantity.

6Power supply:DC24V,33+,34-.

7Cabinet wiring diagram

4、 Touch screen usage instructions:

5、 Communication instructions;

This instrument is equipped with RS485 interface, which can directly communicate with computers (touch screen, PLC),RS485Standard Communicationdistance1.5kmMultiple instruments can be attached.RS232Standard Communicationdistance15mOnly one instrument can be attached.RS232Connect the TXD, RXD, and GND of the interface to the second, third, and fifth pins of the computer serial port, respectively. The data format consists of 1 starting bit, 8 data bits, and noneverify1A stop position.To avoid communication conflicts, the instruments are all in listening mode. The computer sends a command to a certain instrument at a specified address, and then waits for a period of time for the instrument to respond. After the instrument receives the correct command, it sends out the data. After sending, the instrument is in listening mode again. In the same system, instrument addresses cannot be the same, and baud rates must be consistent.

The instrument adopts the standard Modbus rtu communication protocol and supports function numbers 03 and 06. When using configuration software, the device to be selected is a Modicon PLC, Modbus RTU address type, with integer 16 bit data, starting from 4x001 or 4x000 using the Kingview register. Other configuration software may start from 3x001 or 3x000. The communication is an integer, and users need to handle the decimal places according to the actual situation.Communication transmission data is signed integer data, and it is recommended to define signed integer data for user programming. When the data is greater than0x8000When retrieving data, reverse adding is necessary1The actual value that is a negative number, for example, communication transmission data is0xFFFFThe corresponding data value is-1.For long integer data such asAccumulated quantity, etc., data value=high position×65536+Low position. During configuration, users can also choose the data type as long, and the system will automatically calculate the cumulative amount.

Read instrument data and send command format: It is recommended that the amount of data read at once should not exceed16a

address

function number

Starting address high bit

Low order starting address

Read the high bits of data

Read low order of data quantity

CRC16high position

CRC16

low position

01

03

00

00

00

03

05

CB

On site measuring instruments return data format:

address

function number

byte count

High numerical value

numerical value

low position

High numerical value

numerical value

low position

High numerical value

numerical value

low position

CRC16high position

CRC16

low position

01

03

06

03

E8

03

E8

03

E8

C1

9F

Write data to instrument and send command format: (Write to register)

address

function number

Starting address high bit

Low order starting address

Write high bits of data

Low order of the number of data written

CRC16high position

CRC16

low position

01

06

00

20

00

0C

88

05

Data format returned by on-site measuring instruments: (same as the data format sent)

address

function number

Starting address high bit

Low order starting address

Write high bits of data

Low order of the number of data written

CRC16high position

CRC16

low position

01

06

00

20

00

0C

88

05

Example: Read the first measurement value of the instrument with address 1 (PV1=1000)

Send data as 01 03 00 00 00 01 84 0A

The returned data is 01 03 02 03 E8 B8 FA (including 03 E8-1000)

(Among them, 01 is the instrument address, 03 is the function number, 00 00 is the register starting address, 00 01 represents reading a number, 840A is the checksum, and B8 FA in the returned data is the checksum. If you want to read the first and second data, you can send 01 03 00 00 02 C4 0B, and read 16 data and send 01 03 00 00 10 44 06.

Communication measurement value return value=(measurement value+error correction) * full-scale correction. The full correction range is 0.500 to 2.000, and users can also omit this measurement error correction and directly perform error correction on the upper computer.

The communication address range is 1-99, and the baud rate can be set to 2400 or 9600. The instrument has a default communication address of 248 (0XF8), which can be used for testing if the user is unsure. The baud rate is 2400 or 9600. After changing the communication address and baud rate, it needs to be powered on again to take effect.

The instrument has been set with a communication address of 1 and a baud rate of 9600 at the factory.

Register address:

register address

Module address

name call, name, say, weigh

read/write

scope

remark

4X000

1

1Number reaction kettle weighing 1 high 4 positions

read

 

1

4X001

1

1Number reaction kettle weighing 1 low 4 positions

read

 

2

4X002

1

1Number reaction kettle weighing 2 high 4 positions

read

 

3

4X003

1

1Number reaction kettle weighing 2 low 4 positions

read

 

4

4X004

1

1Number reaction kettle weighing 3 high 4 positions

read

 

5

4X005

1

1Number reaction kettle weighing 3 low 4 positions

read

 

6

4X008

1

Valve position feedback input 1

read

 

7

4X009

1

Valve position feedback input 2

read

 

8

4X010

1

Valve position feedback input 3

read

 

9

4X011

1

Temperature input signal

read

 

10

4X026

1

Valve position given signal 1

Read/Write

 

11

4X027

1

Valve position given signal 2

Read/Write

 

12

4X028

1

Valve position given signal 3

Read/Write

 

13

4X016

1

control valve11

Read/Write

 0-1

14

4X017

1

control valve22

Read/Write

 0-1

15

4X018

1

control valve33

Read/Write

 0-1

16

4X019

1

control valve44

Read/Write

 0-1

17

control cabinet1

4X000

2

2Number reaction kettle weighing 1 high 4 positions

read

 

18

4X001

2

2Number reaction kettle weighing 1 low 4 positions

read

 

19

4X002

2

2Number reaction kettle weighing 2 high 4 positions

read

 

20

4X003

2

2Number reaction kettle weighing 2 low 4 positions

read

 

21

4X004

2

2Number reaction kettle weighing 3 high 4 positions

read

 

22

4X005

2

2Number reaction kettle weighing 3 low 4 positions

read

 

23

4X008

2

Valve position feedback input 1

read

 

24

4X009

2

Valve position feedback input 2

read

 

25

4X010

2

Valve position feedback input 3

read

 

26

4X011

2

Temperature input signal

read

 

27

4X026

2

Valve position given signal 1

Read/Write

 

28

4X027

2

Valve position given signal 2

Read/Write

 

29

4X028

2

Valve position given signal 3

Read/Write

 

30

4X016

2

control valve11

Read/Write

 0-1

31

4X017

2

control valve22

Read/Write

 0-1

32

4X018

2

control valve33

Read/Write

 0-1

33

4X019

2

control valve44

Read/Write

 0-1

34

control cabinet1

4X000

3

3Number reaction kettle weighing 1 high 4 positions

read

 

35

4X001

3

3Number reaction kettle weighing 1 low 4 positions

read

 

36

4X002

3

3Number reaction kettle weighing 2 high 4 positions

read

 

37

4X003

3

3Number reaction kettle weighing 2 low 4 positions

read

 

38

4X004

3

3Number reaction kettle weighing 3 high 4 positions

read

 

39

4X005

3

3Number reaction kettle weighing 3 low 4 positions

read

 

40

4X008

3

Valve position feedback input 1

read

 

41

4X009

3

Valve position feedback input 2

read

 

42

4X010

3

Valve position feedback input 3

read

 

43

4X011

3

Temperature input signal

read

 

44

4X026

3

Valve position given signal 1

Read/Write

 

45

4X027

3

Valve position given signal 2

Read/Write

 

46

4X028

3

Valve position given signal 3

Read/Write

 

47

4X016

3

control valve11

Read/Write

 0-1

48

4X017

3

control valve22

Read/Write

 0-1

49

4X018

3

control valve33

Read/Write

 0-1

50

4X019

3

control valve44

Read/Write

 0-1

51

control cabinet1

4X006

1

Backup 01 Reactor Weighing 1 Height 4 Position

read

 

52

4X007

1

Backup 01 reactor weighing 1 low 4 positions

read

53

4X006

2

Backup 02 reactor weighing 1 high 4 positions

read

 

54

4X007

2

Backup 02 reactor weighing 1 low 4 positions

read

55

4X006

3

Backup 03 reactor weighing 1 high 4 positions

read

 

56

4X007

3

Backup 03 reactor weighing 1 low 4 positions

read

57

4X012

1

Valve position feedback input 01 standby

read

 

58

4X013

1

Temperature input signal 01 standby

read

 

59

4X020

3

control valve11

Read/Write

 0-1

60

4X021

3

control valve22

Read/Write

 0-1

61

4X022

3

control valve33

Read/Write

 0-1

62

4X023

3

control valve44

Read/Write

 0-1

63

control cabinet2

4X008

4

Valve position feedback input 1

read

 

64

4X009

4

Valve position feedback input 2

read

 

65

4X010

4

Valve position feedback input 3

read

 

66

4X011

4

Temperature input signal

read

 

67

4X026

4

Valve position given signal 1

Read/Write

 

68

4X027

4

Valve position given signal 2

Read/Write

 

69

4X028

4

Valve position given signal 3

Read/Write

 

70

4X016

4

control valve11

Read/Write

 0-1

71

4X017

4

control valve22

Read/Write

 0-1

72

4X018

4

control valve33

Read/Write

 0-1

73

4X019

4

control valve44

Read/Write

 0-1

74

control cabinet2

4X000

5

5Number reaction kettle weighing 1 high 4 positions

read

 

75

4X001

5

5Number reaction kettle weighing 1 low 4 positions

read

 

76

4X002

5

5Number reaction kettle weighing 2 high 4 positions

read

 

77

4X003

5

5Number reaction kettle weighing 2 low 4 positions

read

 

78

4X004

5

5Number reaction kettle weighing 3 high 4 positions

read

 

79

4X005

5

5Number reaction kettle weighing 3 low 4 positions

read

 

80

4X008

5

Valve position feedback input 1

read

 

81

4X009

5

Valve position feedback input 2

read

 

82

4X010

5

Valve position feedback input 3

read

 

83

4X011

5

Temperature input signal

read

 

84

4X026

5

Valve position given signal 1

Read/Write

 

85

4X027

5

Valve position given signal 2

Read/Write

 

86

4X028

5

Valve position given signal 3

Read/Write

 

87

4X016

5

control valve11

Read/Write

 0-1

88

4X017

5

control valve22

Read/Write

 0-1

89

4X018

5

control valve33

Read/Write

 0-1

90

4X019

5

control valve44

Read/Write

 0-1

91

control cabinet2

4X000

6

6Number reaction kettle weighing 1 high 4 positions

read

 

92

4X001

6

6Number reaction kettle weighing 1 low 4 positions

read

 

93

4X002

6

6Number reaction kettle weighing 2 high 4 positions

read

 

94

4X003

6

6Number reaction kettle weighing 2 low 4 positions

read

 

95

4X004

6

6Number reaction kettle weighing 3 high 4 positions

read

 

96

4X005

6

6Number reaction kettle weighing 3 low 4 positions

read

 

97

4X008

6

Valve position feedback input 1

read

 

98

4X009

6

Valve position feedback input 2

read

 

99

4X010

6

Valve position feedback input 3

read

 

100

4X011

6

Temperature input signal

read

 

101

4X026

6

Valve position given signal 1

Read/Write

 

102

4X027

6

Valve position given signal 2

Read/Write

 

103

4X028

6

Valve position given signal 3

Read/Write

 

104

4X016

6

control valve11

Read/Write

 0-1

105

4X017

6

control valve22

Read/Write

 0-1

106

4X018

6

control valve33

Read/Write

 0-1

107

4X019

6

control valve44

Read/Write

 0-1

108

control cabinet2

4X006

4

Backup 01 Reactor Weighing 1 Height 4 Position

read

 

109

4X007

4

Backup 01 reactor weighing 1 low 4 positions

read

110

4X006

5

Backup 02 reactor weighing 1 high 4 positions

read

 

111

4X007

5

Backup 02 reactor weighing 1 low 4 positions

read

112

4X006

6

Backup 03 reactor weighing 1 high 4 positions

read

 

113

4X007

6

Backup 03 reactor weighing 1 low 4 positions

read

114

4X012

4

Valve position feedback input 01 standby

read

 

115

4X013

4

Temperature input signal 01 standby

read

 

116

4X020

6

control valve11

Read/Write

 0-1

117

4X021

6

control valve22

Read/Write

 0-1

118

4X022

6

control valve33

Read/Write

 0-1

119

4X023

6

control valve44

Read/Write

 0-1

120

6、 System schematic diagram;