Specification of carbon dioxide detector
Date: 2013-07-05Read: 15

  Carbon dioxide detectorApplication scope: Suitable for detecting CO2 concentration in industrial, agricultural, and residential environments, outputting 4-20mA analog signals and 2-channel switch signals. It can directly control the controlled equipment or output data to any electronic analog controller, DDC/PLC controller, or ventilation equipment self-control system, and control the ventilation system based on the monitored target value (CO2 concentration).
  
Equipped with RS-485 communication interface, capable of setting independent addresses, enabling networking with computers and other control systems, and centralized intelligent management of ventilation systems in each room.
  
  Carbon dioxide detectorSpecifications
  
gas detection
  
Carbon dioxide CO2
  
Testing Scope
  
0-2000ppm; 0-3000ppm; 0-5000ppm; 0-10000ppm;
  
Detection Principle
  
NDIR Non Dispersive Infrared Self Diffusion Type
  
Temperature sensing element
  
NTC thermistor
  
power supply
  
12-24DC (direct current)
  
power
  
1.0W/zui 高, 700MW/ 平均
  
precision
  
22 ℃ (72 ℉) ± 30ppm+5% reading
  
stability
  
2% within the service life (15 years)
  
calibration cycle
  
ABCLogic self calibration (no customer calibration required)
  
nonlinear
  
<1%FS
  
reaction time
  
90% change<60 seconds
  
Signal refresh
  
1s
  
warm-up time
  
<2 minutes (operation)
  
10 minutes (highest precision)
  
CO2 measurement range
  
0-2000ppm (default)
  
CO2 display resolution
  
/Set resolution
  
1ppm/1ppm
  
Analog output
  
4-20mA
  
discrete output
  
Two output options are available
  
communication interface
  
RS485, Communication speed 9600
  
traffic
  
Self diffusion 80-120cc/min/inflow 40-50 cc/min
  
Operating Temperature
  
0~75℃
  
Operating Humidity
  
0~95%RH, Not condensing
  
Storage conditions
  
-40~70℃(-40~158℉)
  
NDIR lifespan
  
15 years
  
weight
  
380g
  
Overall dimensions
  
135mm×90mm×34mm