E-mail
59734119@qq.com
-
Phone
13852298983
-
Address
Inside the courtyard at 619 Jinfoil Road, Jiangning District, Nanjing City
Nanjing Huanan Intelligent Technology Co., Ltd
59734119@qq.com
13852298983
Inside the courtyard at 619 Jinfoil Road, Jiangning District, Nanjing City
Carbon dioxide detectorApplication scope: Suitable for detecting CO2 concentration in industrial, agricultural, and residential environments, outputting 4-20mA analog signals and 2-channel switch signals. It can directly control the controlled equipment or output data to any electronic analog controller, DDC/PLC controller, or ventilation equipment self-control system, and control the ventilation system based on the monitored target value (CO2 concentration).
Equipped with RS-485 communication interface, capable of setting independent addresses, enabling networking with computers and other control systems, and centralized intelligent management of ventilation systems in each room.
Carbon dioxide detectorSpecifications
gas detection
Carbon dioxide CO2
Testing Scope
0-2000ppm; 0-3000ppm; 0-5000ppm; 0-10000ppm;
Detection Principle
NDIR Non Dispersive Infrared Self Diffusion Type
Temperature sensing element
NTC thermistor
power supply
12-24DC (direct current)
power
1.0W/zui 高, 700MW/ 平均
precision
22 ℃ (72 ℉) ± 30ppm+5% reading
stability
2% within the service life (15 years)
calibration cycle
ABCLogic self calibration (no customer calibration required)
nonlinear
<1%FS
reaction time
90% change<60 seconds
Signal refresh
1s
warm-up time
<2 minutes (operation)
10 minutes (highest precision)
CO2 measurement range
0-2000ppm (default)
CO2 display resolution
/Set resolution
1ppm/1ppm
Analog output
4-20mA
discrete output
Two output options are available
communication interface
RS485, Communication speed 9600
traffic
Self diffusion 80-120cc/min/inflow 40-50 cc/min
Operating Temperature
0~75℃
Operating Humidity
0~95%RH, Not condensing
Storage conditions
-40~70℃(-40~158℉)
NDIR lifespan
15 years
weight
380g
Overall dimensions
135mm×90mm×34mm
Last Article: Precautions for using the four in one detector
Next Article: Introduction to Oxygen Analyzer