✅ Ideal location:
Stay away from sources of interference: Avoid approaching the feed inlet, mixer, or heating coil to prevent liquid level fluctuations or steam interference.
Avoid obstacles: Ensure that the antenna beam is not obstructed by tank walls, brackets, or internal structures (recommended distance from tank walls ≥ 300mm).
Vertical installation: The antenna should be perpendicular to the liquid surface, with a tilt angle of ≤ 5 °, to avoid signal reflection and offset.
❌ Avoid location:
Foam or steam accumulation area (such as near the steam outlet).
Strong vibration or impact areas (such as pump outlet).
| Installation method | Applicable scenarios | Precautions |
|---|---|---|
| Flange installation | Standard storage tanks and pressure vessels | Ensure that the sealing gasket is resistant to medium corrosion (such as PTFE). |
| threaded installation | Small tanks and pipelines | Thread specification matching (such as G1 half, NPT1 '). |
| Installation of waveguide rod | Viscous media (asphalt, sludge) | The waveguide rod should be vertical to avoid bending. |
| Installation of bypass pipe | High viscosity or easily crystallizable medium | The diameter of the bypass pipe is ≥ 80mm, which is convenient for maintenance. |
Cable selection:
Shielded twisted pair cables (such as AWG18) to avoid electromagnetic interference.
Armored cables (Ex d certified) are used in explosion-proof areas.
Grounding requirements:
The transmitter housing and cable shielding layer need to be reliably grounded (grounding resistance<4 Ω).
Avoid sharing grounding with motors and frequency converters to prevent interference.
Empty tank calibration: When there is no medium in the tank, set the "zero point" to 4mA (or 0%).
Full range setting: Enter the actual tank height (such as 10m) and adjust the corresponding value of 20mA.
Echo curve optimization:
Use the echo curve analysis function to filter false signals (such as condensate, foam).
Adjust the signal threshold to ensure that only real liquid level echoes are recognized.