It must be installed vertically to ensure that the flange end face of the container is vertical and to avoid glass tube breakage.
It is prohibited to use magnetic materials such as iron wire for fixing. It is recommended to use non-magnetic materials such as copper pipes as heat tracing pipelines.
During installation, a valve should be installed between the liquid level gauge and the container inlet pipe to facilitate debugging, maintenance, and cleaning.
The tested medium should not contain solid impurities or magnetic substances to avoid blocking the float.
Regularly clean the main pipe and remove impurities (when the ordinary level gauge exceeds 3 meters or the anti-corrosion type exceeds 2 meters, reinforced flanges need to be added).
Before use, it is necessary to use calibrated magnetic steel to set the zero position flip column in red and the rest in white.
When debugging, first open the upper inlet valve, and then slowly open the lower valve to avoid the medium impacting the float.
Daily maintenance requires monitoring of container pressure sealing conditions and regular cleaning of glass tubes.
Liquid level gauges exceeding 3 meters (ordinary type) or 2 meters (anti-corrosion type) require the installation of a reinforced flange in the middle.
Install away from material inlet and outlet to avoid local fluid changes affecting measurement accuracy.