1. Accuracy: better than 0.5%;
2. Nonlinear distortion: better than 0.5%;
3. Rated working voltage:+24V ± 20%, maximum working voltage: ≤ 35V;
4. Power consumption: Static 4mA, dynamic equal to loop current, internal limit 25mA+10%;
5. Rated input: 5A... 1KA (38 specifications);
6. Perforation core diameter: 8, 9, 12, 20, 25, 30mm;
7. Output format: two-wire DC4-20mA;
8. Temperature drift coefficient of output current: ≤ 50ppm/℃;
9. Response time: ≤ 100mS;
10. Input/output insulation isolation strength:>AC3000V, 1min, 1mA;
11. Output load resistance: RL=V+-10V/0.02 (Ω);
Note: (1) The load impedance at standard V+24V is 700 Ω;
(2) RL=250 Ω conversion resistor for 1-5V+total copper resistance of two transmission lines.
12. Input overload protection: 30 times for 1 minute;
13. Output overcurrent limit protection: internal limit 25mA+10%;
Note: (1) * Standard output overcurrent limit protection: internal limit 25mA+10%;
(2) Customized according to customer requirements: internal limit 22mA+10%, 24mA+10%.
14. Transient induction lightning and surge current TVS suppression protection capability for two-wire ports: TVS suppresses surge current of 35A/20ms/1.5KW;
15. The two-wire port is equipped with+24V power reverse protection;
16. The output current setting has a long-term short-circuit protection limit; Internal limit of 25mA+10%;
17. Working environment: -40 ℃ -80 ℃, 10% -90% RH;
18. Storage temperature: -50 ℃ -85 ℃;
19. Execution standard: GB/T13850-1998;
20. Series model, specifications, wiring diagram, product appearance, product photos, safety precautions.