DS310 Intelligent Wireless High and Low Voltage Tester
DS310 Intelligent Wireless High and Low Voltage TesterComposed of hook type voltage testers, telescopic insulation rods, receivers, etc., unlike traditional voltage testers that only test a single voltage level, fully intelligent voltage testing ranges from 1V to 550kV or higher voltage levels. When the bare wire voltage exceeds 60kV, non-contact electrical testing is used, and the tester gradually approaches the wire to complete the testing without touching the wire. For bare wires below 60kV, the voltage tester can be hung on the circuit for contact testing. Whether it is neutral wire, live wire, ground wire, high-voltage transmission line or metal conductor, as long as there is electricity, it may be direct transmission of electricity or leakage caused by insulation damage. The fully intelligent voltage tester can sense its electric field and emit a buzzing sound. The stronger the electric field near the wire, the more rapid the buzzing sound, warning that there is electricity.
The voltage tester can be hung on bare wires below 60kV for testing. It can be hung on wires or cables with a large outer diameter of 168mm, or on busbars with a large size of 168mm × 245mm, saving the operator's physical energy. The wireless high-voltage voltage tester has a straight-line receiving distance of about 160 meters, and the receiver adopts a 3.5-inch true color LCD screen with dynamic display, which is intuitive and clear. Insulated rods are lightweight, moisture resistant, high temperature resistant, impact resistant, highly insulated, and stretchable. Widely used in substations, power plants, fire departments, industrial and mining enterprises, as well as testing stations and electrical maintenance departments for electrical testing and field electrical operations.
Function |
High voltage electrical testing, frequency testing, electric field judgment, etc |
power supply |
DC 3.7VRechargeable lithium battery, can work continuously for about 8-12 hours when fully charged |
Electrical verification method |
Contact type electrical testing: Bare wires below 60kV can be directly hung on the circuit for testing; Non contact electrical testing: Non contact testing is used for lines above 60kV. |
transmission method |
433MHzwireless transmission |
transmission distance |
The straight-line distance is about 160m |
display mode |
3.5Inch true color LCD screen dynamic display |
Hanging wire diameter |
A 168mm wire or cable, or a 168mm × 245mm busbar |
Scope of electrical testing |
1V~550kV (50Hz/60Hz automatic) |
Frequency: 45Hz~75Hz | |
Resolution |
0.1Hz |
Frequency accuracy |
± 2Hz (voltage above 36V) |
Induction intensity adjustment |
When checking the electricity, press the left and right arrow keys to adjust the induction intensity of the electric field. The left arrow key weakens and the right arrow key strengthens, with several levels including 100V, 1000V, 10Kv, and 100Kv. It is suitable for places with dense power lines. When turned on, the default level is 100V with strong induction. |
Insulation rod size |
Approximately 5m in length after stretching; approximately 1m in length after shrinking (5 sections) |
data storage |
9999group |
sampling rate |
1~2 times/second |
Instrument size |
Hook type voltage tester: length, width, and thickness 310mm × 270mm × 52mm Wireless receiver: length, width, and thickness 250mm x 100mm x 40mm |
line voltage |
60kVThe following bare wires can be directly contacted for testing; Bare wires above 60kV must undergo non-contact testing, and the voltage tester should gradually approach the tested wire. |
data retention |
Press the HOLD key to hold the data in test mode, and then press the HOLD key to cancel the hold |
Exit function |
Press the ESC key to exit the current function interface and return to the higher-level directory |
Contact electrical testing |
Contact voltage tester can only be hung in Zone A of hook type voltage tester |
Data retrieval |
After entering the data lookup mode, use the arrow keys to browse through the stored data |
No signal indication |
Dynamic display when the receiver does not receive the transmission signalThe words' No connection signal ' |
Auto Shutdown |
After about 15 minutes of startup, the instrument panel automatically shuts down to reduce battery consumption |
battery voltage |
When the battery voltage is below 3.2V, the low battery voltage symbol is displayed to remind charging |
Instrument quality |
Hook type voltage tester: 486g (including battery) Receiver: 1.45kg (including battery) Total weight: 11.5kg (including insulation rod and battery) |
Operating temperature and humidity |
-10℃~40℃; Below 80% Rh |
Storage temperature and humidity |
-10℃~60℃; Below 70% Rh |
Wireless interference |
No interference from 433MHz same frequency signals |
insulation strength |
Insulation pole: AC 110kV/rms (after stretching all 5 insulation poles, between both ends) Electrical tester: 2000V/rms (between the insulation rod connector and the top of the hook type detector) Receiver: 2000V/rms (front and rear ends of the casing) |
Structure |
Anti drip type II |
Hook type voltage tester |
1Taiwan |
wireless receiver |
1Taiwan |
antenna |
2root |
Telescopic insulating rod |
1root |
instrument box |
1a |
charger |
1a |
lithium battery |
2Block (inside the instrument) |
User manual/warranty card/certificate of conformity |
1set |