Precautions for using a single flange liquid level transmitter:
1. When measuring liquid pressure, the installation position of the single flange level transmitter should avoid the impact of the liquid (i.e. water hammer phenomenon) to prevent damage to the sensor due to overpressure.
When freezing occurs in winter, anti freezing measures must be taken for the single flange liquid level transmitter installed outdoors to prevent the liquid in the pressure inlet from expanding due to freezing volume and causing damage to the sensor.
3. When wiring a single flange liquid level transmitter, thread the cable through a waterproof joint (accessory) or flexible tube and tighten the sealing nut to prevent rainwater and other substances from leaking into the transmitter housing through the cable.
4. When measuring liquid pressure with a single flange level transmitter, the pressure tap should be opened on the side of the process pipeline to avoid sedimentation and slag accumulation.
5. To prevent the single flange liquid level transmitter from coming into contact with corrosive or overheated media, and to prevent slag from depositing in the conduit.
6. When measuring gas pressure, the pressure tap should be opened at the top of the process pipeline, and the flange level transmitter should also be installed at the upper part of the process pipeline to allow the deposited liquid to be quickly injected into the process pipeline.
7. The single flange liquid level transmitter should pay attention to installing the pressure pipe of the sensor in a place with small temperature fluctuations.
8. When measuring steam or other high-temperature media with a single flange liquid level transmitter, a condenser such as a buffer tube (coil) should be connected, and the operating temperature of the transmitter should not exceed the limit.