Instructions for Using XMZ-J-A Series Patrol Inspection Instrument
Date: 2022-10-17Read: 13

I. Overview

XMZ-J-AThe series touring inspection instrument is an intelligent instrument that uses computer technology. The instrument adopts a dual row digital tube to display the current channel number and corresponding measurement value simultaneously. The current channel also has indicator lights for display, which can be displayed at a fixed point or in a loop. The common upper limit alarm and upper limit alarm contacts are output,Each channel alarm value can be independently set, and thermocouple and thermistor signals can be freely input, which can be integrated with a computerRS485Serial communication or driver micro print timing printing, communication protocol adopts internationally recognizedModbustuAgreement, able to communicate withPLCOr the touch screen can be connected to form a centralized control and management system.

2、 Technical performance indicators

1Accuracy: ±0.5%F·S±1.0One word. Note: The sensor needs to be isolated from the external metal casing.

2Input signal and temperature measurement range:K(0~1300℃)、E(0~800℃)、J(0~1000℃)、S(0~1600℃)、R(0~1700℃)、

N(0~1400℃)、Pt100(-200.0~600.0℃)TheCu50(-50.0~150.0℃)

3Alarm relay contact capacity:220V 3A(obstructive)

4Working power supply: AC220V±10% 50HZPower consumption less than5W

5Normal working environment: temperature0~50℃, relative humidity35%~85%Non corrosive gas environments

3、 Instrument model definition

This instrument is1~16Road universal patrol inspection instrument, pre-set at the factory according to customer needs.

XMZ□ - J □ □ □

1 2 3 4

“1”Instrument appearance:A:96×96×110 Opening:92×92 Space:160×80×120 Opening:152×76

“2”: represents the number of channels: such as‘16’For16通道,‘8’For8通道。

“3”Alarm definition:‘0’No alarm‘1’Equipped with an upper limit alarm‘2’With2Road limit alarm‘3’Upper and lower limit alarm

“4”: Suffix:‘D’Equipped with a micro printer“R2” beltRS232Serial communication interface“R4” beltRS485Serial communication interface, 'space' does not have this function

4Instrument panel layout (reference)

11111.jpg


5、 Operation of instruments

1The normal display status of the instrument

① In normal use, the upper display window shows the temperature value measured in the current channel, the lower display window shows the current channel number, and the current channel also has indicator lights displayed. When setting parameters, the lower row displays the parameter symbol and the upper row displays the set value.

② PressSETkey3In seconds, you can enter the parameter menu and press the ▼ or ▲ keys to set any value within the specified range for the parameters. Long press the ▼ or ▲ keys to achieve quick addition or subtraction; pressSETPress the ▼ key to exit the menu halfway.

③ In automatic inspection mode, press the ▼ or ▲ key3SEnter channel fixed-point or loop display setting status,Press the ▼ or ▲ keys to set the value of the lower window to1~LUWhen there is a certain number of channels, the instrument will display the measured value of that channel at a fixed point,Set this value to0Or pressSETkey,The instrument returns to the cyclic display state,

④ When there is an alarm output, the alarm indicator light is on. If there is an upper limit alarm, the corresponding channel indicator light will flash; If the lower limit alarm is triggered, the corresponding channel indicator light will remain on.

⑤Printing function time parameter setting (only available with printing function):

Simultaneously hold downSETKey&▼ key, ▲ key, three keys3For seconds or more, enter the printing time setting state.

2Setting of basic parameters of instruments

serial number

Address

symbol

name

set the scope

Instructions

factory default




The lower window displays:

Designated inspection channel number

fromLudecide

(0~16)

When users need to perform fixed-point inspections on a certain channel, they can set the parameter value to the channel number. If the value is0When, it is in automatic inspection mode

0

0

0000H

LC

combination lock

0~255

LC=18When, all parameter values can be modified

18

1

0001H

Sn

Sensor input type

-

Pt100(-200.0~600.0℃)TheCu50(-50.0~150.0℃)

K(0~1300℃)、E(0~800℃)、J(0~1000℃)、

S(0~1600℃)、R(0~1700℃)、N(0~1400℃)

-

2

0002H

dp

display precision

0~1

dp=0No decimal point; dp=1Display decimal point

0

3

0003H

Lu

Channel number setting

1~LP

Users can adjust the required number of channels within the factory value range

-

4

0004H

t1

Inspection interval time

4~120second

The user can set this parameter to customize the inspection interval time

4

5

0005H

t2

Mailing Address/

print time

1~9999

When using serial communication function‘t2’Indicate the communication address for each channel

When equipped with printing function‘t2’Indicates the timed interval printing time (in minutes)

-

6

0006H

bt

Baud rate

-

1200 、2400、4800、9600(Printing function is meaningless)

9600

7

0007H

LP

For factory testing purposes




8

0008H

OP

Output mode selection

0~2

0: None 1: WithRS485Communication function 2: With printing function

-

9

0009H

L1

第1Road limit alarm

Full range

When measuring temperature>L1At this time, an upper limit alarm is generated (the indicator light is constantly on)

-

....


....





24

0018H

L16

第16Road limit alarm

Full range

When measuring temperature>L16At this time, an upper limit alarm is generated (the indicator light is constantly on)

-

25

0019H

F1

第1road

Upper limit alarm

Full range

When measuring temperature>F1At this time, an upper limit alarm is generated (the indicator light is constantly flashing)

-

....


....





40

0028H

F16

第16road

Upper limit alarm

Full range

When measuring temperature>F16time,Generate upper limit alarm (indicator light constantly flashing)

-

41

0029H

C1

第1Road error correction

±20.0

Sensor error correction

0.0

....


....




0.0

56

0038H

C16

第16Road error correction

±20.0

Sensor error correction

0.0

6、 Instrument wiring (reference):

222222.jpg


Note: 1Printer interface wiring, this instrument usesTTLLevel interface method, ‘R’Connect the printer's busy line‘T’Connect the printer data cable,GNDConnect the printer to the ground wire, other wires do not need to be connected.

2The communication and printing functions of the instrument cannot be combined at the same time, choose one of the two.

7、 Attention:
1
The equipped sensors must be isolated type.
2
If all the numbers on the instrument display jumping, please check if the working voltage of the instrument is normal and make it comply with the regulations.

3After being powered on, it continues to display on the upper display window“HH”Please check if the sensor is disconnected, short circuited, or if there are any other wiring issues. 4If any channel experiences an upper limit alarm,Then the channel indicator light will turn on, ALM1The light is on,The relay is engaged;If any channel experiences an upper limit alarm,Then the channel indicator light will flash, ALM2The light is on,The relay is engaged.

5Found that the parameters cannot be changed, please check‘LC’Is it18.