I. Overview
XMZ-J-AThe series touring inspection instrument is an intelligent instrument that uses computer technology. The instrument adopts a dual row digital tube to display the current channel number and corresponding measurement value simultaneously. The current channel also has indicator lights for display, which can be displayed at a fixed point or in a loop. The common upper limit alarm and upper limit alarm contacts are output,Each channel alarm value can be independently set, and thermocouple and thermistor signals can be freely input, which can be integrated with a computerRS485Serial communication or driver micro print timing printing, communication protocol adopts internationally recognizedModbustuAgreement, able to communicate withPLCOr the touch screen can be connected to form a centralized control and management system.
2、 Technical performance indicators
1Accuracy: ±0.5%F·S±1.0One word. Note: The sensor needs to be isolated from the external metal casing.
2Input signal and temperature measurement range:K(0~1300℃)、E(0~800℃)、J(0~1000℃)、S(0~1600℃)、R(0~1700℃)、
N(0~1400℃)、Pt100(-200.0~600.0℃)TheCu50(-50.0~150.0℃)
3Alarm relay contact capacity:220V 3A(obstructive)
4Working power supply: AC220V±10% 50HZPower consumption less than5W
5Normal working environment: temperature0~50℃, relative humidity35%~85%Non corrosive gas environments
3、 Instrument model definition
This instrument is1~16Road universal patrol inspection instrument, pre-set at the factory according to customer needs.
XMZ□ - J □ □ □
1 2 3 4
“1”Instrument appearance:A:96×96×110 Opening:92×92 Space:160×80×120 Opening:152×76
“2”: represents the number of channels: such as‘16’For16通道,‘8’For8通道。
“3”Alarm definition:‘0’No alarm‘1’Equipped with an upper limit alarm‘2’With2Road limit alarm‘3’Upper and lower limit alarm
“4”: Suffix:‘D’Equipped with a micro printer“R2” beltRS232Serial communication interface“R4” beltRS485Serial communication interface, 'space' does not have this function
4Instrument panel layout (reference)

5、 Operation of instruments
1The normal display status of the instrument
① In normal use, the upper display window shows the temperature value measured in the current channel, the lower display window shows the current channel number, and the current channel also has indicator lights displayed. When setting parameters, the lower row displays the parameter symbol and the upper row displays the set value.
② PressSETkey3In seconds, you can enter the parameter menu and press the ▼ or ▲ keys to set any value within the specified range for the parameters. Long press the ▼ or ▲ keys to achieve quick addition or subtraction; pressSETPress the ▼ key to exit the menu halfway.
③ In automatic inspection mode, press the ▼ or ▲ key3SEnter channel fixed-point or loop display setting status,Press the ▼ or ▲ keys to set the value of the lower window to1~LUWhen there is a certain number of channels, the instrument will display the measured value of that channel at a fixed point,Set this value to0Or pressSETkey,The instrument returns to the cyclic display state,
④ When there is an alarm output, the alarm indicator light is on. If there is an upper limit alarm, the corresponding channel indicator light will flash; If the lower limit alarm is triggered, the corresponding channel indicator light will remain on.
⑤Printing function time parameter setting (only available with printing function):
Simultaneously hold downSETKey&▼ key, ▲ key, three keys3For seconds or more, enter the printing time setting state.
2Setting of basic parameters of instruments
serial number |
Address |
symbol |
name |
set the scope |
Instructions |
factory default |
|
The lower window displays: Designated inspection channel number |
fromLudecide (0~16) |
When users need to perform fixed-point inspections on a certain channel, they can set the parameter value to the channel number. If the value is0When, it is in automatic inspection mode |
0 |
|||
0 |
0000H |
LC |
combination lock |
0~255 |
LC=18When, all parameter values can be modified |
18 |
1 |
0001H |
Sn |
Sensor input type |
- |
Pt100(-200.0~600.0℃)TheCu50(-50.0~150.0℃) K(0~1300℃)、E(0~800℃)、J(0~1000℃)、 S(0~1600℃)、R(0~1700℃)、N(0~1400℃) |
- |
2 |
0002H |
dp |
display precision |
0~1 |
dp=0No decimal point; dp=1Display decimal point |
0 |
3 |
0003H |
Lu |
Channel number setting |
1~LP |
Users can adjust the required number of channels within the factory value range |
- |
4 |
0004H |
t1 |
Inspection interval time |
4~120second |
The user can set this parameter to customize the inspection interval time |
4 |
5 |
0005H
|
t2 |
Mailing Address/ print time |
1~9999 |
When using serial communication function‘t2’Indicate the communication address for each channel When equipped with printing function‘t2’Indicates the timed interval printing time (in minutes) |
- |
6 |
0006H |
bt |
Baud rate |
- |
1200 、2400、4800、9600(Printing function is meaningless) |
9600 |
7 |
0007H |
LP |
For factory testing purposes |
|||
8 |
0008H |
OP |
Output mode selection |
0~2 |
0: None 1: WithRS485Communication function 2: With printing function |
- |
9 |
0009H |
L1 |
第1Road limit alarm |
Full range |
When measuring temperature>L1At this time, an upper limit alarm is generated (the indicator light is constantly on) |
- |
.... |
.... |
|||||
24 |
0018H |
L16 |
第16Road limit alarm |
Full range |
When measuring temperature>L16At this time, an upper limit alarm is generated (the indicator light is constantly on) |
- |
25 |
0019H |
F1 |
第1road Upper limit alarm |
Full range |
When measuring temperature>F1At this time, an upper limit alarm is generated (the indicator light is constantly flashing) |
- |
.... |
.... |
|||||
40 |
0028H |
F16 |
第16road Upper limit alarm |
Full range |
When measuring temperature>F16time,Generate upper limit alarm (indicator light constantly flashing) |
- |
41 |
0029H |
C1 |
第1Road error correction |
±20.0 |
Sensor error correction |
0.0 |
.... |
.... |
0.0 |
||||
56 |
0038H |
C16 |
第16Road error correction |
±20.0 |
Sensor error correction |
0.0 |
6、 Instrument wiring (reference):

Note: 1Printer interface wiring, this instrument usesTTLLevel interface method, ‘R’Connect the printer's busy line‘T’Connect the printer data cable,GNDConnect the printer to the ground wire, other wires do not need to be connected.
2The communication and printing functions of the instrument cannot be combined at the same time, choose one of the two.
7、 Attention:
1The equipped sensors must be isolated type.
2If all the numbers on the instrument display jumping, please check if the working voltage of the instrument is normal and make it comply with the regulations.
3After being powered on, it continues to display on the upper display window“HH”Please check if the sensor is disconnected, short circuited, or if there are any other wiring issues. 4If any channel experiences an upper limit alarm,Then the channel indicator light will turn on, ALM1The light is on,The relay is engaged;If any channel experiences an upper limit alarm,Then the channel indicator light will flash, ALM2The light is on,The relay is engaged.
5Found that the parameters cannot be changed, please check‘LC’Is it18.