I. Overview
XMT-J400WAThe instrument is a four-way temperature controller that can be connected simultaneously4Road sensors, sensor input types, alarm modes, and control cycles can be independently set for each channel, with independent self-tuning modesPIDParameters and simultaneous control4Road temperature and4Road alarm, precise and reliable control performance of the whole machine.
2、 Technical indicators
1Input type: CU50(-50.0~150.0℃)、Pt100(-19.9~600.0℃)、
K(0~1300℃)TheE(0~700.0℃)、 J(0~900.0℃)、
T(-200~400.0℃)TheS(0~1600℃)、R(0~1700℃)、
WR25(0~2300℃)、N(-200~1200℃)TheB(0~1800℃)、
0~5V(0~10MA)、1~5V(4~20MA) Note: Analog input requires explanation before ordering
note①The equipped sensor must be an isolated type (i.e. sensor)2The root lead is insulated from the external metal protective tube.
note②When the usersomeOne input signal is0~5V、1~5VWhen simulating signals, the input type cannot be changed to thermocouple or thermistor signals because the hardware of the instrument is incompatible with thermocouple and thermistor signals. But the settings between thermocouple and thermistor signals can be changed arbitrarily.
2Control mode: Two position controlPIDcontrol
3Relay output: Relay220V 5A(resistive load)
4Solid state relay drive signal: current greater than15mAThe no-load voltage is greater than12VThe cycle is approximately2S
5Measurement accuracy: ±0.5F·S±1Words, additional cold end correction error ±1℃
6Working power supply:AC85~242V 50/60Hz Power consumption: less than4W
7Working environment:0~50℃, relative humidity ≤85%RHIn non corrosive and non strong electromagnetic radiation environments
8External dimensions(mm): 160×80×110 cutout size:152×76
96×96×110 cutout size:92×92
IIIBasic settings and operations
1First level menu settings
Press the function key(SETKey)3In seconds, enter the first level menu, and at this point, '...'1Road display window 'and' Section '2The 'road display window' displays parameter symbols and parameter values respectively. You can press the ◄ (shift key), ▲, and ▼ keys to change the parameter values. After modification, pressSETSave key to enter the next parameter; Modify other parameters using the same method.
serial number |
Prompt symbol |
register address |
name call, name, say, weigh |
set the scope |
Instructions |
factory default |
|
|
one level dish single |
0 |
LocK |
0000H |
combination lock |
0~50 |
LocK=18Allow modification of all parameters, LocK≠18It is prohibited to modify all parameters. |
18 |
1 |
OPb |
0001H |
Secondary output mode |
0~2 |
0: No secondary output; 1:RS485Serial communication (requires hardware support) 2: With printing record function (hardware support required) |
0 |
|
2 |
Add |
0002H |
Mailing Address |
1~64 |
The numbering of instruments in the centralized control system |
1 |
|
3 |
bAUd |
0003H |
Baud rate |
0~3 |
0:1200; 1:2400; 2:4800; 3:9600; |
9600 |
|
2Secondary menu settings
Each channel parameter is adjusted according toCH1TheCH2TheCH3TheCH4Three seconds to enter the corresponding channel menu item, you can press the ◄, ▲, ▼ keys to change the parameter values. After completing the modification, pressSETSave key to enter the next parameter; The parameters are shown in the table below:
|
dish single
|
4 |
SU 1 |
0004H |
Temperature setpoint |
dIL~dIH |
第1Channel control point temperature setting parameters |
100.0 |
5 |
AL 1 |
0005H |
alarm setpoint |
dIL~dIH |
fromALP1Parameters determine the alarm mode See detailsALP1Parameter Description |
150.0 |
|
6 |
SC 1 |
0006H |
Error correction value |
±20.0 |
第1Translation correction value for channel sensor error. newPV1=oldPV1+SC1 |
0.0 |
|
|
7 |
P 1 |
0007H |
proportional band |
0~200.0 |
P≠0When, the instrument isPIDControl mode.adoptPIDWhen controlling, the proportional band determines the magnitude of the system's proportional gain,PThe larger the proportion, the smaller the effect and the smaller the overshoot, but too small will increase the heating time. P=0When the instrument is in position control (hysteresis control) mode;Some actuators that are not suitable for frequent start-up (such as fans, compressors, motors, etc.) should use this method, as specified in the parametersHy1The explanation section. |
15.0 |
|
|
8 |
I 1 |
0008H |
integration time |
0~3000 |
Set the integration time to eliminate residual deviations caused by proportional control,Too much will delay the time for the system to reach equilibrium,Too small can cause fluctuations |
240 |
|
9 |
d 1 |
0009H |
differential time |
0~200 s |
Set differential time to prevent output fluctuations,Improve the stability of control |
30 |
|
|
10 |
Hy 1 |
000AH |
Main control and alarm return difference |
0.1~50.0 |
When the instrument is in position control (hysteresis control) mode(P1=0)The main control loop is only effective. backlashHy1It refers to the dead zone between the opening or closing of the actuator, and setting the hysteresis value can avoid frequent actions of the actuator. When the main control is in heating mode: When measuring valuesPV1≤ Set valueSU1-Hy1When, the actuator opens; whenPV1≥SU1+Hy1When, the actuator closes. |
1.0 |
|
11 |
t 1 |
000BH |
Output cycle |
0~120 s |
Set the action cycle for relay control |
10 |
|
12 |
dp 1 |
000CH |
Decimal point position |
0~1 |
0: Do not display decimal point; 1: Display after decimal point1Position; 2: Display after decimal point2Bit (only available for analog quantities); 3: Display after decimal point3Bit (only available for analog quantities); Note: OnlySn=0~5Vor1~5Vtime Ability to set2Position or3Decimal point. |
1 |
|
|
13 |
ALP 1 |
000DH |
alarm method |
0~6 |
0: No alarm; 1: Upper limit alarm; 2: Lower limit alarm; 3:Upper deviation alarm; 4Deviation alarm below; 5Alarm outside the interval; 6Alarm within the interval; |
1 |
|
|
14 |
Sn 1 |
000EH |
Input specifications |
0~12 |
0:CU50(-50.0~150.0℃)、 1:Pt100(-199.9~600.0℃)、 2:K(0~1300℃)、 3:E(0~700.0℃)、 4:J(0~900.0℃)、 5:T(-200~400.0℃、 6:S(0~1600℃)、 7:R(0~1700℃)、 8:WR25(0~2300℃)、 9:N(-200~1200℃)、 10:B(0~1800℃)、 11:0~5V(0~10ma)Hardware support is required 12:1~5V(4~20ma)Hardware support is required |
K |
|
15 |
dIL 1 |
000FH |
Lower limit of set value |
Range starting point~dIH |
This parameter limits the lower limit of the set value |
random |
|
16 |
dIH 1 |
0010H |
Set the upper limit of the value |
dIL~Full range |
This parameter limits the upper limit of the set value |
random |
|
17 |
At 1 |
0011H |
Self-tuning parameters |
0~1 |
0: Disable self-tuning 1: Enable self-tuning |
0 |
|
18 |
Coo 1 |
0012H |
heat/refrigeration |
0~1 |
0Heating function 1Cooling function |
0 |
|
Two channels |
three-channel |
four-channel |
||||||||
19 |
SU 2 |
0013H |
34 |
SU 3 |
0022H |
49 |
SU 4 |
0031H |
||
20 |
AL 2 |
0014H |
35 |
AL 3 |
0023H |
50 |
AL 4 |
0032H |
||
21 |
SC 2 |
0015H |
36 |
SC 3 |
0024H |
51 |
SC 4 |
0033H |
||
22 |
P 2 |
0016H |
37 |
P 3 |
0025H |
52 |
P 4 |
0034H |
||
23 |
I 2 |
0017H |
38 |
I 3 |
0026H |
53 |
I 4 |
0035H |
||
24 |
d 2 |
0018H |
39 |
d 3 |
0027H |
54 |
d 4 |
0036H |
||
25 |
Hy 2 |
0019H |
40 |
Hy 3 |
0028H |
55 |
Hy 4 |
0037H |
||
26 |
t 2 |
001AH |
41 |
t 3 |
0029H |
56 |
t 4 |
0038H |
||
27 |
dp 2 |
001BH |
42 |
dp 3 |
002AH |
57 |
dp 4 |
0039H |
||
28 |
ALP 2 |
001CH |
43 |
ALP 3 |
002BH |
58 |
ALP 4 |
003AH |
||
29 |
Sn 2 |
001DH |
44 |
Sn 3 |
002CH |
59 |
Sn 4 |
003BH |
||
30 |
dIL 2 |
001EH |
45 |
dIL 3 |
002DH |
60 |
dIL 4 |
003CH |
||
31 |
dIH 2 |
001FH |
46 |
dIH 3 |
002EH |
61 |
dIH 4 |
003DH |
||
32 |
At 2 |
0020H |
47 |
At 3 |
002FH |
62 |
At 4 |
003EH |
||
33 |
Coo 2 |
0021H |
48 |
Coo 3 |
0030H |
63 |
Coo 4 |
003FH |
||
3Set the given values for each channel
pressCH1TheCH2TheCH3TheCH4Three seconds to enter the corresponding channel menu item (secondary menu), appearsSUParameter, press the ◄, ▲, ▼ keys to modify the parameter value, pressSETSave key.
6、 Self tuning operation
First, set the settings and then enter the menu,Set the hysteresis as0.5~1Left and right, willATset to1The instrument enters the self-tuning state, and the corresponding display window flashes“AT”At this point, the instrument is in positional control, and after three oscillations, the instrument determines a new onePTheIThedWait for the parameters and save them, then reset the instrument and enter the control state.
7Fault analysis and troubleshooting
1When the instrument window displays“HHorLL”Please check if the sensor wiring is correct.
2When it is found that the temperature between channels affects each other, please check whether the equipped sensors are isolated.
8、 Communication ProtocolThe communication function is optional and needs to be explained before orderingIf communication function is not required, there is no need to read this section
1The communication baud rate is1200、2400、4800、9600Four adjustable levels, data format is1A starting position8A data bit,1A stop bit without a checksum. The parameters that need to be set on the instrument include:OPbTheAddCommunication device address (instrument number)btCommunication baud rate.
2Read parameters from the upper computer(support1-4a character)
Instrument Number |
function code(03) |
First address of parameter register |
Number of words read(1~4) |
CRC16 |
1byte |
1byte |
2byte |
2byte |
2byte |
3Instrument response:(1-4a character)
Instrument Number |
function code(03) |
Number of bytes read |
parameter value1 |
...... |
parameter value4 |
CRC16 |
1byte |
1byte |
1byte |
2byte |
N*2byte |
2byte |
2byte |
4Write a parameter on the upper computer(1One word),The format of the instrument response frame is the same:
Instrument Number |
function code(06) |
First address of parameter register |
parameter value |
CRC16 |
1byte |
1byte |
2byte |
2byte |
2byte |
in the above tableCRC16Verification code according to standardModbustuCommunication protocol calculation, with low bits at the beginning and high bits at the end.
5The parameter code and register address can be found in the instrument manual<Menu parameter table>.
6Besides<Menu parameter table>In addition to the register addresses in, the following table shows several commonly used register addresses. (Note ①)
|
OUTTheATTheALstate Register Address (Note 2) |
measured valuePV register address |
set valueSU register address |
decimal pointdP register address |
|||||
decimal |
16numeral system |
decimal |
16numeral system |
decimal |
16numeral system |
decimal |
16numeral system |
|
a passage |
6144 |
1800H |
6145 |
1801H |
6146 |
1802H |
6147 |
1803H |
Two channels |
6148 |
1804H |
6149 |
1805H |
6150 |
1806H |
6151 |
1807H |
three-channel |
6152 |
1808H |
6153 |
1809H |
6154 |
180AH |
6155 |
180BH |
four-channel |
6156 |
180CH |
6157 |
180DH |
6158 |
180EH |
6159 |
180FH |
Note 1: For each channel mentioned above4Each register only supports continuous global reading. For example: using03Function code, read once6144~6147The instrument will also return four parameter values at once for the four consecutive register addresses in.
Note 2: The address is6144、6148、6152、6156The data stored in the register isWORD, containing16aBITThe information is as follows:
D7 |
D6 |
D5 |
D4 |
D3 |
D2 |
D1 |
D0 |
AT |
AL |
AL=1An alarm will occur;AT=1The instrument is in a self-tuning state;D0~D7To output percentage(0~100).
7For the convenience of users, we also store the measurement values of the four channels in the following consecutive register address blocks, which also support one-time reading.
One channel measurement valuePV1 |
Two channel measurement valuesPV2 |
Three channel measurement valuesPV3 |
Four channel measurement valuesPV4 |
|
|
register address |
4097(Decimal) |
4098(Decimal) |
4099(Decimal) |
4100(Decimal) |
1001H(16Base system) |
1002H(16Base system) |
1003H(16Base system) |
1004H(16Base system) |
9、 Supplementary Explanation for Communication
1The program part of the upper computer for writing data to the instrument should add parameter limiting function according to the specifications of the instrument to prevent data beyond the range from being written to the instrument,
Make it unable to function properly. Please refer to the previous "Instrument Manual" for the parameter codes, register addresses, and rangesThe menu table in.
2The interval time for the upper computer to send read or write instructions should be greater than or equal to0.1Second, if it's too short, the instrument may not be able to respond in time.
3The measured value is32767(7FFFH)ExpressingHH(Beyond the upper range), for32512(7F00H)ExpressingLL(Exceeding the lower range)
4BesidesCRCVerify that the low bits of the byte are in the front and outside,All other double bytes have high bits in front.
5The instrument has not sent decimal point information, so it should be set as needed when programming the upper computer.
6Single bus mounting20The communication quality below the station is relatively stable. If more mounting is required, it is best to connect to ensure communication stability485Repeater.
7Because there are some on the marketmodbusThe first address of the parameter register address for smart devices is from1At the beginning, some0Start (this instrument)
from0Start). Therefore, when communicating with some configuration software or touch screens, all parameter register addresses of the instruments in the table above need to be
plus1To read and write correctly.