Instructions for using XMT-J400WA four channel controller
Date: 2021-10-16Read: 10

I. Overview

XMT-J400WAThe instrument is a four-way temperature controller that can be connected simultaneously4Road sensors, sensor input types, alarm modes, and control cycles can be independently set for each channel, with independent self-tuning modesPIDParameters and simultaneous control4Road temperature and4Road alarm, precise and reliable control performance of the whole machine.

2、 Technical indicators

1Input type: CU50(-50.0~150.0℃)、Pt100(-19.9~600.0℃)、

K(0~1300℃)TheE(0~700.0℃)、 J(0~900.0℃)、

T(-200~400.0℃)TheS(0~1600℃)、R(0~1700℃)、

WR25(0~2300℃)、N(-200~1200℃)TheB(0~1800℃)、

0~5V(0~10MA)、1~5V(4~20MA) Note: Analog input requires explanation before ordering

note①The equipped sensor must be an isolated type (i.e. sensor)2The root lead is insulated from the external metal protective tube.

note②When the usersomeOne input signal is0~5V、1~5VWhen simulating signals, the input type cannot be changed to thermocouple or thermistor signals because the hardware of the instrument is incompatible with thermocouple and thermistor signals. But the settings between thermocouple and thermistor signals can be changed arbitrarily.

2Control mode: Two position controlPIDcontrol

3Relay output: Relay220V 5A(resistive load)

4Solid state relay drive signal: current greater than15mAThe no-load voltage is greater than12VThe cycle is approximately2S

5Measurement accuracy: ±0.5F·S±1Words, additional cold end correction error ±1℃

6Working power supply:AC85~242V 50/60Hz Power consumption: less than4W

7Working environment:0~50℃, relative humidity ≤85%RHIn non corrosive and non strong electromagnetic radiation environments

8External dimensions(mm): 160×80×110 cutout size:152×76

96×96×110 cutout size:92×92

IIIBasic settings and operations

1First level menu settings

Press the function key(SETKey)3In seconds, enter the first level menu, and at this point, '...'1Road display window 'and' Section '2The 'road display window' displays parameter symbols and parameter values respectively. You can press the ◄ (shift key), ▲, and ▼ keys to change the parameter values. After modification, pressSETSave key to enter the next parameter; Modify other parameters using the same method.

serial number

Prompt symbol

register

address

name call, name, say, weigh

set the scope

Instructions

factory default

one

level

dish

single

0

LocK

0000H

combination lock

0~50

LocK=18Allow modification of all parameters,

LocK≠18It is prohibited to modify all parameters.

18

1

OPb

0001H

Secondary output mode

0~2

0: No secondary output;

1:RS485Serial communication (requires hardware support)

2: With printing record function (hardware support required)

0

2

Add

0002H

Mailing Address

1~64

The numbering of instruments in the centralized control system

1

3

bAUd

0003H

Baud rate

0~3

0:1200;

1:2400;

2:4800;

3:9600;

9600

2Secondary menu settings

Each channel parameter is adjusted according toCH1TheCH2TheCH3TheCH4Three seconds to enter the corresponding channel menu item, you can press the ◄, ▲, ▼ keys to change the parameter values. After completing the modification, pressSETSave key to enter the next parameter; The parameters are shown in the table below:

First Channel Menu: PressCH1Three second entry

dish

single

4

SU 1

0004H

Temperature setpoint

dIL~dIH

第1Channel control point temperature setting parameters

100.0

5

AL 1

0005H

alarm setpoint

dIL~dIH

fromALP1Parameters determine the alarm mode

See detailsALP1Parameter Description

150.0

6

SC 1

0006H

Error correction value

±20.0

第1Translation correction value for channel sensor error.

newPV1=oldPV1+SC1

0.0

7

P 1

0007H

proportional band

0~200.0

P≠0When, the instrument isPIDControl mode.adoptPIDWhen controlling, the proportional band determines the magnitude of the system's proportional gain,PThe larger the proportion, the smaller the effect and the smaller the overshoot, but too small will increase the heating time.

P=0When the instrument is in position control (hysteresis control) mode;Some actuators that are not suitable for frequent start-up (such as fans, compressors, motors, etc.) should use this method, as specified in the parametersHy1The explanation section.

15.0

8

I 1

0008H

integration time

0~3000

Set the integration time to eliminate residual deviations caused by proportional control,Too much will delay the time for the system to reach equilibrium,Too small can cause fluctuations

240

9

d 1

0009H

differential time

0~200 s

Set differential time to prevent output fluctuations,Improve the stability of control

30

10

Hy 1

000AH

Main control and alarm return difference

0.1~50.0

When the instrument is in position control (hysteresis control) mode(P1=0)The main control loop is only effective. backlashHy1It refers to the dead zone between the opening or closing of the actuator, and setting the hysteresis value can avoid frequent actions of the actuator.

When the main control is in heating mode:

When measuring valuesPV1≤ Set valueSU1-Hy1When, the actuator opens; whenPV1≥SU1+Hy1When, the actuator closes.

1.0

11

t 1

000BH

Output cycle

0~120 s

Set the action cycle for relay control

10

12

dp 1

000CH

Decimal point position

0~1

0: Do not display decimal point;

1: Display after decimal point1Position;

2: Display after decimal point2Bit (only available for analog quantities);

3: Display after decimal point3Bit (only available for analog quantities);

Note: OnlySn=0~5Vor1~5Vtime

Ability to set2Position or3Decimal point.

1

13

ALP 1

000DH

alarm method

0~6

0: No alarm;

1: Upper limit alarm;

2: Lower limit alarm;

3:Upper deviation alarm;

4Deviation alarm below;

5Alarm outside the interval;

6Alarm within the interval;

1

14

Sn 1

000EH

Input specifications

0~12

0:CU50(-50.0~150.0℃)、

1:Pt100(-199.9~600.0℃)、

2:K(0~1300℃)、

3:E(0~700.0℃)、

4:J(0~900.0℃)、

5:T(-200~400.0℃、

6:S(0~1600℃)、

7:R(0~1700℃)、

8:WR25(0~2300℃)、

9:N(-200~1200℃)、

10:B(0~1800℃)、

11:0~5V(0~10ma)Hardware support is required

12:1~5V(4~20ma)Hardware support is required

K

15

dIL 1

000FH

Lower limit of set value

Range starting point~dIH

This parameter limits the lower limit of the set value

random

16

dIH 1

0010H

Set the upper limit of the value

dIL~Full range

This parameter limits the upper limit of the set value

random

17

At 1

0011H

Self-tuning parameters

0~1

0: Disable self-tuning 1: Enable self-tuning

0

18

Coo 1

0012H

heat/refrigeration

0~1

0Heating function 1Cooling function

0

Two channels


three-channel


four-channel

19

SU 2

0013H

34

SU 3

0022H

49

SU 4

0031H

20

AL 2

0014H

35

AL 3

0023H

50

AL 4

0032H

21

SC 2

0015H

36

SC 3

0024H

51

SC 4

0033H

22

P 2

0016H

37

P 3

0025H

52

P 4

0034H

23

I 2

0017H

38

I 3

0026H

53

I 4

0035H

24

d 2

0018H

39

d 3

0027H

54

d 4

0036H

25

Hy 2

0019H

40

Hy 3

0028H

55

Hy 4

0037H

26

t 2

001AH

41

t 3

0029H

56

t 4

0038H

27

dp 2

001BH

42

dp 3

002AH

57

dp 4

0039H

28

ALP 2

001CH

43

ALP 3

002BH

58

ALP 4

003AH

29

Sn 2

001DH

44

Sn 3

002CH

59

Sn 4

003BH

30

dIL 2

001EH

45

dIL 3

002DH

60

dIL 4

003CH

31

dIH 2

001FH

46

dIH 3

002EH

61

dIH 4

003DH

32

At 2

0020H

47

At 3

002FH

62

At 4

003EH

33

Coo 2

0021H

48

Coo 3

0030H

63

Coo 4

003FH

3Set the given values for each channel

pressCH1TheCH2TheCH3TheCH4Three seconds to enter the corresponding channel menu item (secondary menu), appearsSUParameter, press the ◄, ▲, ▼ keys to modify the parameter value, pressSETSave key.

6、 Self tuning operation

First, set the settings and then enter the menu,Set the hysteresis as0.5~1Left and right, willATset to1The instrument enters the self-tuning state, and the corresponding display window flashes“AT”At this point, the instrument is in positional control, and after three oscillations, the instrument determines a new onePTheIThedWait for the parameters and save them, then reset the instrument and enter the control state.

7Fault analysis and troubleshooting

1When the instrument window displays“HHorLL”Please check if the sensor wiring is correct.

2When it is found that the temperature between channels affects each other, please check whether the equipped sensors are isolated.

8、 Communication ProtocolThe communication function is optional and needs to be explained before orderingIf communication function is not required, there is no need to read this section

1The communication baud rate is1200、2400、4800、9600Four adjustable levels, data format is1A starting position8A data bit,1A stop bit without a checksum. The parameters that need to be set on the instrument include:OPbTheAddCommunication device address (instrument number)btCommunication baud rate.

2Read parameters from the upper computer(support1-4a character)

Instrument Number

function code(03)

First address of parameter register

Number of words read(1~4)

CRC16

1byte

1byte

2byte

2byte

2byte

3Instrument response:(1-4a character)

Instrument Number

function code(03)

Number of bytes read

parameter value1

......

parameter value4

CRC16

1byte

1byte

1byte

2byte

N*2byte

2byte

2byte

4Write a parameter on the upper computer(1One word),The format of the instrument response frame is the same:

Instrument Number

function code(06)

First address of parameter register

parameter value

CRC16

1byte

1byte

2byte

2byte

2byte

in the above tableCRC16Verification code according to standardModbustuCommunication protocol calculation, with low bits at the beginning and high bits at the end.

5The parameter code and register address can be found in the instrument manual<Menu parameter table>.

6Besides<Menu parameter table>In addition to the register addresses in, the following table shows several commonly used register addresses. (Note ①)


OUTTheATTheALstate

Register Address (Note 2)

measured valuePV

register address

set valueSU

register address

decimal pointdP

register address

decimal

16numeral system

decimal

16numeral system

decimal

16numeral system

decimal

16numeral system

a passage

6144

1800H

6145

1801H

6146

1802H

6147

1803H

Two channels

6148

1804H

6149

1805H

6150

1806H

6151

1807H

three-channel

6152

1808H

6153

1809H

6154

180AH

6155

180BH

four-channel

6156

180CH

6157

180DH

6158

180EH

6159

180FH

Note 1: For each channel mentioned above4Each register only supports continuous global reading. For example: using03Function code, read once6144~6147The instrument will also return four parameter values at once for the four consecutive register addresses in.

Note 2: The address is6144、6148、6152、6156The data stored in the register isWORD, containing16aBITThe information is as follows:

D7

D6

D5

D4

D3

D2

D1

D0





AT



AL

AL=1An alarm will occur;AT=1The instrument is in a self-tuning state;D0~D7To output percentage(0~100).

7For the convenience of users, we also store the measurement values of the four channels in the following consecutive register address blocks, which also support one-time reading.


One channel measurement valuePV1

Two channel measurement valuesPV2

Three channel measurement valuesPV3

Four channel measurement valuesPV4

register

address

4097(Decimal)

4098(Decimal)

4099(Decimal)

4100(Decimal)

1001H(16Base system)

1002H(16Base system)

1003H(16Base system)

1004H(16Base system)

9、 Supplementary Explanation for Communication

1The program part of the upper computer for writing data to the instrument should add parameter limiting function according to the specifications of the instrument to prevent data beyond the range from being written to the instrument,

Make it unable to function properly. Please refer to the previous "Instrument Manual" for the parameter codes, register addresses, and rangesThe menu table in.

2The interval time for the upper computer to send read or write instructions should be greater than or equal to0.1Second, if it's too short, the instrument may not be able to respond in time.

3The measured value is32767(7FFFH)ExpressingHH(Beyond the upper range), for32512(7F00H)ExpressingLL(Exceeding the lower range)

4BesidesCRCVerify that the low bits of the byte are in the front and outside,All other double bytes have high bits in front.

5The instrument has not sent decimal point information, so it should be set as needed when programming the upper computer.

6Single bus mounting20The communication quality below the station is relatively stable. If more mounting is required, it is best to connect to ensure communication stability485Repeater.

7Because there are some on the marketmodbusThe first address of the parameter register address for smart devices is from1At the beginning, some0Start (this instrument)

from0Start). Therefore, when communicating with some configuration software or touch screens, all parameter register addresses of the instruments in the table above need to be

plus1To read and write correctly.