Based on the actual situation on site, the Xun'er team has developed targeted solutions for customers, matching corresponding flow meters, temperature sensors, and pressure sensors according to the customer's on-site caliber, temperature, flow range, etc., to ensure measurement accuracy and stability.
In terms of flowmeter selection, we chose an electromagnetic flowmeter for the customer because the design temperature of the primary network is usually 130 ℃ for water supply and 70 ℃ for return water, using F46 lining. The design temperature of the secondary network is generally 80 ℃ for water supply and 60 ℃ for return water, using PTFE lining. The circulating water has a single composition and no corrosiveness, so we chose 316L electrode.
Considering that heating is usually only carried out in winter, and the sealing measures of heat exchange stations are not very good, indoor and outdoor hot and cold air may meet, and water vapor is prone to condensation. Therefore, IP68 protection level is selected. And configure appropriate temperature and pressure sensors.