How to choose a suitable level gauge for a water tank
Date: 2022-10-27Read: 12

We often encounter customers sending on-site pictures of water tanks without specifying which type of level gauge they want. Customers often require us to provide a quotation and select a suitable level gauge that meets their requirements and is both cost-effective. As a senior customerManufacturer of liquid level gaugeLet's have a brief discussion with our clients:

Let's first take a look at the technical requirements. The design specifications for the high-level water tank are as follows:

1. The water tank adopts stainless steel plate water tank, and the method is shown in 12 s101. The inlet and outlet pipe valves should be equipped with indication opening and closing devices. When installed outdoors on the top of the star, protective measures such as locks or door boxes should be taken for the manhole of the water tank and the valves of the inlet and outlet pipes. The insulation of accessories such as the water tank and provincial road valves should be made of rubber sheets (pipes) with a thickness of 30mm and covered with aluminum foil.

2. The high-level water tank should be firmly connected to the foundation.

3. The overflow pipe and ventilation pipe of the water tank (pool) are all equipped with stainless steel mesh covers (18 mesh). The method is shown in 12s101-73-75. The vertical distance between the water outlet and the water surface is not less than 250mm. The method is shown in 12s101-71, and the cover cushion is sealed with rubber pads.

4. Local and transmission code level gauges should be installed at the high-level water tank to display the bottom elevation, highest effective water level, highest alarm water level, lowest alarm water level, and lowest effective water level.

5. Control and Signal:

5.1 The booster pump of the indoor fire hydrant system is automatically started by the pressure switch set on the outlet pipe of the indoor fire hydrant pump and the flow switch set on the outlet pipe of the high-level water tank.

5.2 The control cabinet or control panel should be able to display high water level, low water level alarm signals, and normal water level of the high-level water tank.


The customer needs to transmit the displayed liquid level gauge both locally and remotelyLevel gauge functionIt is displayed locally and can achieve remote transmission output function. Can actually display the liquid level height. The function of highest level alarm and lowest level alarm.

We are looking at the customer's water tank diagram;

3

The height of the water tank is 2.5 meters, the overflow water level is 2250mm, the maximum temperature alarm size is 2200mm, and the minimum level alarm size is 2150mm. Based on the above judgment, the effective range of the liquid level gauge is 2300mm

Based on the above customer requirements, our company has provided quotations for two products: a 2.3-meter magnetic flap level gauge with remote transmitter function and a static pressure level gauge, which will be paired with a liquid level display box. It can achieve liquid level display and high/low level alarm function.

5