Functional characteristics of JBJY-3000C insulated boots (gloves) voltage withstand test device
Date: 2017-03-27Read: 4

Functional characteristics of JBJY-3000C insulated boots (gloves) voltage withstand test device

1、 Overview:

JBJY-3000CThe voltage withstand test device for insulated boots (gloves) is a batch testing equipment designed and produced by our company in accordance with the requirements of the "Preventive Test Regulations for Power Safety Tools" issued by the State Power Company, and in response to feedback from users. This product effectively solves the problem of non-standard testing in the past, improves work efficiency, and ensures work safety. It is a device for insulation boots (gloves) withstand voltage testing.

2、 Technical parameters

1Power supply voltage220V 50HZ

2Rated power1.5KVA

3Rated output voltage50KV

4Digital display, equipped with zero position, overcurrent, timing, and alarm functions.

2、 Usage:

After unpacking, fix the testing device and connect the grounding wire.

2. Before the experiment, fill the test sample with steel balls and adjust the electrode rod by locking the screw. Insert the electrode into the insulating boot (glove) and adjust the screw to make contact with the steel ball surface.

3. Remote control button“3”For the stop button, "4" is the start button, "2" is the boost button, "1" is the buck button, "5" is the timer button, and "6" is the backup button.

4. Connect the power and press the air switch,The power indicator light is on,Press down“4”The key and high voltage indicator light are on. If they are not on, it means that the regulator has not reset to zero. Please press“1”Press the button to lower the voltage, and then press it“4”Press the key again“2”Key boost,When the required voltage is reached, press“5”Key, start timing,When the buzzer sounds, press it“1”Key, regulator returns to zero, press“3”Key to end the experiment.

5.The * block gauge from the left is a high voltage gauge(KV),behind6Block meter is an intelligent ammeter(mA). ,6Block Table(mA)The corresponding indicator light above is an overcurrent indicator light,One by one correspondence.