WDAS-500 DC Circuit Breaker Ampere Second Characteristics Tester Product Introduction
Date: 2025-11-25Read: 8

WDAS-500 DC Circuit Breaker Ampere Second Characteristics Tester

2、 Functional Features

1. Automatic measurement of circuit breaker tripping time at any current, automatic generation of constant high current with high precision and strong load capacity.

2. Adopting advanced microcomputer control technology to achieve accurate measurement of the ampere second characteristics of DC circuit breakers

3. Adopting a large screen LCD display (320 * 240 dot matrix) with a fully Chinese interface, it is easy to operate and convenient to use

4. The equipment has self-protection function to ensure the reliability and reliability of testing

5. It can be controlled and operated by a computer, and the ampere second characteristic curve can be measured through management software. It can also be automatically tested for ampere second characteristics on a single machine

6. It can store 100 test records without losing them in case of power failure, and can upload data to the computer through RS232 or USB flash drive.

7. By controlling the management software, test data can be stored and printed.

8WDAS-500 DC Circuit Breaker Ampere Second Characteristics TesterCan perform circuit breaker cascade testing

3、 Technical indicators

model

  


WDAS-500

  


WDAS-1000

  


WDAS-2000

  


Working Voltage

  


AC220 10%

  


AC220 10%

  


AC380 10%

  


Z large output current

  


500A

  


1000A

  


2000A

  


Output current stability

  


1%

  


1%

  


1%

  


Current adjustment range

  


1~500A

  


1~1000A

  


1~2000A

  


Time measurement accuracy

  


1ms

  


1ms

  


1ms

  


working environment

  


Temperature -20 ℃ -60 ℃, humidity 20% -80% RH

  


Storage conditions

  


-Packaging and storage at 20 ℃ -70 ℃

  


contact method

  


RS232 communication and USB communication

  


display mode

  


5.7 'industrial grade LCD, 320 × 240