Welcome Customer !
ybzhanCorporate NewsPay attention to these points when operating the insulated glove boot voltage tester

Insulated glove boot voltage testerCan reliably identify parameters such as leakage current, insulation aging, and power frequency withstand voltage of insulated gloves (boots) and insulated rods, and can simultaneously detect six insulated gloves (boots) and multiple insulated rods; The function testing device for the voltage tester can test the starting voltage and anti-interference performance of the voltage tester. Below are some precautions for using this device.

Precautions for operating the insulated glove voltage tester:

1. Connect the working circuit according to the experiment you conducted. The casing of the test transformer and the casing of the operating system must be reliably grounded. The X end (high voltage tail) of the high-voltage winding used for testing the transformer and the F end of the measuring winding must be reliably grounded.

2. Before turning on the power, the voltage regulator of the operating system must be set to zero before the power can be turned on, closed, and the boost can begin.

3. The voltage starts from zero and rises at a certain speed to the desired test voltage, while closely monitoring the values of each voltage and current on the display screen and the condition of the test sample. If any abnormal data display or test condition is found during the boosting process or testing process, the voltage should be immediately reduced, the power should be cut off, and a grounding wire should be hung on the high-voltage side to investigate the situation.

4. After the experiment is completed, the voltage regulator should be returned to zero at a constant speed within a few seconds, and then the power should be cut off.

5. This product shall not be used beyond its rated parameters.

6. In case of special circumstances, please quickly press the emergency switch to cut off the power supply.