AOB192P-2X1 Digital Active Power Meter (Intelligent Type) -120x120
AOB192P-2X1 Digital Active Power Meter (Intelligent Type) -120x120

Product detailed manual download ()
Name: Digital Active Power Meter (Intelligent Type)
Model: AOB192P-2X1
Specifications:AC 380V/220V 5A variable ratio adjustable
Power supply: AC/DC85~264V
Hole: 111x111mm
Usage: It can be used in any environment with high interference, such as frequency converters, soft starters, thyristor voltage regulators, inverters (for photovoltaic projects), etc.
1、 Overview
1.1 Purpose
AOB19 intelligent programmable digital power meter is a new generation of programmable smart meters, mainly used for real-time measurement and indication of active power in single-phase or three-phase power lines, and remote transmission of measured power data through RS485 interface or analog transmission output interface.
1.2 Functional Features
Adopting a modular design approach, the voltage and current transformer multiplier of the full SMT production process can be freely set
One channel analog transmission output function (optional), the output can be programmed to be 0-10mA, 0-20mA, 4-20mA at will
One way lower limit alarm output or two-way switch remote control output function (optional), alarm action delay time can be set arbitrarily within the range of 0-60s
RS485 communication output function (optional), using standard MODBUS-RTU communication protocol
It can simultaneously have one analog transmission, one lower limit alarm, and RS485 communication output functions
Two or four switch status detection function (optional), combined with RS485 communication to achieve "remote signaling" and "telemetry" of switch status
Maximum and minimum value viewing function
2、 Technical parameters
2.1 Active power measurement display range: 0~999W~999kW~9999MW (unit automatically switched through status indicator light)
2.2 Reactive power measurement display range: 0~999var~999kvar~9999Mvar (unit automatically switches through status indicator light)
2.3 Measurement accuracy: ± 0.5% FS1) 1 (± word (active power, ± 1.0% FS ± word reactive power)
2.4 Rated input voltage: AC100V, 220V, 380V (transformer multiplier can be freely set)
2.5 Rated input current: AC 1A or 5A (transformer multiplier can be freely set)
2.6 Input signal frequency range: 45.00-65.00Hz
2.7 Input circuit power consumption: voltage<1VA, current<0.5VA
2.8 Resolution: up to 1W, decimal point automatically shifted
2.9 Sampling rate: approximately 3 times per second
2.10 Overflow indication: Display characters "HHHH" or "LLLL"
2.11 Polarity indication: can display reverse power, negative signal automatically displays "-"
2.12 Auxiliary power supply: AC/DC 85-264V Power consumption:<3VA
2.13 Alarm output: The upper and lower limit alarms are output by the same relay, with contact capacities of AC250V/2A and DC30V/2A.
2.14 Transmission output: can be freely set to DC0~10mA 0 20mA or 4~20mA,
Accuracy ± 0.5% FS, electrical isolation between signal input and auxiliary power supply, output load resistance: ≤ 500 Ω
2.15 Communication interface: RS485 serial communication, using MODBUS-RTU communication protocol
2.16 Communication baud rate: optional 1200bit/s, 2400bit/s, 4800bit/s, 9600bit/s
2.17 Working environment: Non corrosive environment with temperature ranging from -10 to 50 ℃ and humidity ≤ 85% RH