AOB194H-7X1 Digital Power Factor Meter (Intelligent Type) -72x72
AOB194H-7X1 Digital Power Factor Meter (Intelligent Type) -72x72

Product detailed manual download ()
Name: Digital Power Factor Meter (Intelligent Type)
Model: AOB194H-7X1
Specifications:AC 220V 5A (input phase voltage and current)
Power supply: AC/DC85~264V
Hole: 67x67mm
Usage: It can be used in any environment with high interference, such as frequency converters, soft starters, thyristor voltage regulators, inverters (for photovoltaic projects), etc.
1、 Overview
1.1 Purpose
AOB19 intelligent programmable digital display power factor and phase meter is a new generation of programmable intelligent meter, mainly used for real-time measurement and indication of power factor and phase (power factor angle) values in single-phase or three-phase power lines, and through RS485 interface or analog transmission output interface, it can be used to provide real-time measurement and indication of the power factor and phase (power factor angle) values in single-phase or three-phase power lines
Remote transmission of electricity measurement data.
1.2 Technical Features
Adopting modular design approach and full SMT production process
While real-time measuring and displaying power factor values, phase and frequency measurement values can also be viewed through the instrument keyboard
One channel analog transmission output function (optional), the output can be programmed to be 0-10mA, 0-20mA, 4-20mA at will
One way lower limit alarm output or two-way switch remote control output function (optional), alarm action delay time can be set arbitrarily within the range of 0-60s
RS485 communication output function (optional), using standard MODBUS-RTU communication protocol
It can simultaneously have one analog transmission, one lower limit alarm, and RS485 communication output functions
Two or four switch status detection function (optional), combined with RS485 communication to achieve "remote signaling" and "telemetry" of switch status
Maximum and minimum value viewing function
3、 Technical parameters
3.1 Power factor measurement display range: 0.000C~0.500C~1.000~0.500L~0.000L
3.2 Phase measurement display range: 0 ° to 359.9 °
3.3 Frequency measurement display range: 30.00-99.99 Hz
3.4 Measurement accuracy: The power factor accuracy is ± 0.01, the phase measurement accuracy is ± 1 °, and the frequency measurement accuracy is ± 0.1Hz
3.5 Resolution: The power factor display resolution is 0.001, the frequency display resolution is 0.01Hz, and the phase display resolution is 0.1 °
3.6 Sampling rate: about 3 times/s
3.7 Rated input voltage: AC100V ± 10%, 220V ± 10%, 380V ± 10%
3.8 Input current: 1-5A
3.9 Input circuit power consumption: voltage<1VA, current<0.5VA
3.10 Auxiliary power supply: AC/DC85-264V 50/60Hz
3.11 Auxiliary power consumption:<3VA
3.12 Prompt message when there is no signal input: display the character "----"
3.13 Alarm output: The upper and lower limit alarms have the same relay output contact capacity of AC250V/2A and DC30V/2A.
3.14 Transmission output: can be freely set to DC0-10mA, 0-20mA or 4-20mA, accuracy ± 0.5% FS, electrically isolated from signal input and auxiliary power supply
3.15 Transmission output load resistance: ≤ 500 Ω
3.16 Communication interface: RS485 serial communication, using MODBUS-RTU communication protocol
3.17 Working environment: Non corrosive environment with temperature ranging from -10 to 50 ℃ and humidity ≤ 85% RH