HP-510Digital power meter (0.2 level)It is a multifunctional digital power meter for measuring single-phase (1P/2W) AC/DC power supply. This product has a testing bandwidth of DC0.5Hz~100kHz. Equipped with a 5 "IPS LCD display, 5-digit measurement display, multi parameter synchronous measurement, and high-precision measurement capability. And it also has waveform display function (voltage/current/power), integral measurement function, measurement and analysis of various harmonics (50/60Hz measurement meets the requirements of IEC61000-4-7), external sensor input terminals, and various communication interfaces to assist users in achieving clear, convenient, and accurate power measurement.

B、 Digital power meter (0.2 level)Features of the equipment
1.5'HDIPSLCD resolution up to 854 * 480
2. DC, 0.5HZ-100kHZ voltage/current testing with bandwidth
3. Waveform display: V voltage, 1 current, P power
4. The voltage/current can measure abnormal waves with a CF of 3, and the half range CF can reach 6
Measurement and analysis of harmonics of order 5.50 (numerical and bar chart)
6. External current sensor input terminal EXT1
7. Standard interface RS-232C, USB
8. Harmonic measurement meets the requirements of IEC61000-4-7 (50/60Hz)
9. Two numerical display modes
10. General mode: Display 2 main parameters and 8 secondary parameters
11. Simple mode: Display 4 main parameters
C、 technical indicators
1. Accuracy of ammeter: ±(0.1%reading+0.1%range+1One word)
2. Resolution of ammeter:0.001A(0.001A~9.999A)
0.01A(10.00A~20.00A)
3. Range of ammeter:1A/5A/10A/20A
4. Accuracy of voltmeter: ±(0.4%reading+0.1range+1One word)
5. Resolution of voltmeter:0.1V
6. Range of voltmeter:15V/30V/60V/150V/300V/600V
7. Measurement accuracy of power meter: ±[0.4%reading+(0.1/PF)%range+1a character]
8. Resolution of power meter:0.1W(0.1W~999.9W);1W(1.000KWAbove)
9. Power factor measurement accuracy: ±[0.001/reading+0.001×(1+0.02f)+1a character]
10. Power factor meter force:0.001
11. Harmonic measurement symbol andIEC61000-4-7requirement(50/60Hz)Total harmonic wave of voltage and current2-50Sub harmonic value test.
12. Input bandwidth:DC0.5Hz-100KHz