Schematic diagram of cross-section of shielding room Application areas: It is mainly used for metrological testing, information security, EMC testing and other fields that require high shielding performance
Schematic diagram of cross-section of shielding room

Schematic diagram of cross-section of shielding room

Application areas:It is mainly used in metrology testing, information security, EMC testing and other fields that require high shielding performance.
characteristic:Easy to disassemble, aesthetically pleasing, lightweight
Structural composition:
1. Shell: There are six panel bodies and insulation treatment between the shell and the ground. The six panel body is composed ofδ =1.5mm cold-rolled steel plate (can also be thickened) is used to make unit modules, which are assembled through M8 galvanized bolts, nuts, washers, and conductive pads after galvanizing and spraying; The electromagnetic sealing is reliable and the assembly and disassembly process is strong.
Actual schematic diagram of the shielding room shell wall panel:

2. Platform screen door: electrically (manually) locked platform screen door, basic specifications 1.9 * 0.85 (mm). Customized according to customer requirements(Manual available)/Electric/The distinction).
3. Ventilation waveguide window: Install honeycomb ventilation waveguide windows according to the specifications of the shielding room, with a basic size of 300× 300 (mm).
4. Shielded indoor ventilation system; Indoor separate air conditioning (equipped with air conditioning shielding treatment) and central air conditioning (connected to air conditioning vents and ventilation ducts) for ventilation.
5. Power filter: single-phase high-performance low leakage filter.(There are specific power levels)
6. Shielding indoor weak current communication system: corresponding to shielding processing for telephone, fire protection, network, video, monitoring, data line communication transmission, etc.
7. Indoor electrical: Indoor configuration includes distribution boxes, incandescent lamps and embedded fluorescent lamp blocks for lighting, cable routing, control switches, and wall sockets.
8. Interior decoration: decorate the roof, walls, and floor separately according to user requirements
Top: Ceiling keel+Micro porous aluminum plate
Wall: Light steel keel+double-sided plastic aluminum plate
Location: Activity bracket+all steel anti-static activity floor
Assembled performance indicators(Unit: dB
| medium |
magnetic field |
electric field |
plane wave |
microwave |
| frequency |
14kHz |
150KHz |
200K~50MHzHz |
50MHz~1GHz |
1GHz~10GHz |
| HLS1 |
≥70 |
≥95 |
≥100 |
≥100 |
≥80 |
Test standard: GB12190-2006
|