- Phone
- Address
Chengdu Xinhaosi Electronic Detection Technology Co., Ltd
| Detection object: Methane | Detection principle: catalytic combustion type |
| Detection range: (3-100)% LEL | Communication method: XBUS dual bus |
| Working voltage: DC24V | Signal output: 1 set of sound and light alarm control output (24V/50mA), 2 sets of passive switch signal (contact quantity: 1A/DC24V) |
| Power consumption: ≤ 1W | Main material: Aluminum alloy |
| Connection thread: G3/4 "internal thread * 2 | Explosion proof mark: Ex d IIC T6 Gb |
| Protection level: IP66 | Installation methods: through pipe installation, top mounted installation, wall mounted installation (fixed with screws), wall mounted installation (fixed with L-shaped angle iron) |
| Usage environment: Temperature (-40~+70) ℃ (catalytic combustion) Humidity ≤ 95% RH (no condensation) Pressure (86~106) kPa | |