1HS2858 Variable Frequency Series (Parallel) Resonance Test EquipmentOverview
Variable frequency string(And))The complete set of resonant testing equipment is based on the principle of series resonance, using an excitation transformer to excite the series(And)Connected resonant circuit, controlled by adjusting frequency conversion
The output frequency of the device causes series resonance between the reactor inductance and the sample capacitance in the circuit, and the resonance voltage is the voltage applied to the sample. The frequency conversion resonance test device is widely used in industries such as power, metallurgy, petroleum, and chemical engineering, and is suitable for the handover and preventive testing of high-capacity, high-voltage capacitive specimens.
IIHS2858 Variable Frequency Series (Parallel) Resonance Test EquipmentMain Features
●System measurement accuracy: Level 1 ●Working temperature range: -10~45 ℃ ●Working humidity range: ≤ 90% ●Altitude: ≤ 1500m
●Power supply voltage: 380V ± 10%, three-phase or 220V ± 10%, single-phase (10KW and below) 50/60Hz
●Power supply capacity: 0-300KW ●Working frequency range: 30-300Hz (frequency range can also be relaxed according to user requirements)
●Rated output voltage: 0-1000KV● Rated output capacity: 0-35MVA ● Reactor Q value: 30-120
●Frequency adjustment resolution: 0.02Hz;●Instability ≤ 0.05%●Output waveform: sine wave, waveform distortion rate ≤ 1%
●The system has fully automatic protection such as IGBT, overvoltage, overcurrent, and sample flashover●Noise: ≤ 60dB
Configuration Table of Voltage Endurance Devices for 35kV and Below Cables:
Product model name |
control box |
Reactor (dry-type) |
Excitation transformer (dry-type) |
voltage divider |
Scope of Application |
HS2858/22 |
2.5kW |
1A/22kV two units |
2.5kVA/1kV |
25kV |
10kV cable ≤ 1km |
HS2858/22 |
4kW |
Two 2A/22kV units |
4kVA/1kV |
25kV |
10kV cable ≤ 2km |
HS2858/22 |
6kW |
2A/22kV three units |
6kVA/1/3kV |
60kV |
10kV cable ≤ 3km 35kV cable ≤ 1km |
HS2858/22 |
7.5kW |
Four 2A/22kV units |
7.5kVA/1/3kV |
60kV |
10kV cable ≤ 4km 35kV cable ≤ 1km |
HS2858/22 |
10kW |
Six 2A/22kV units |
10kVA/1/3kV |
60kV |
10kV cable ≤ 6km 35kV cable ≤ 2km |
HS2858/22 |
15kW |
Six units of 2.5A/22kV |
15kVA/1/3kV |
100kV |
10kV cable ≤ 8km 35kV cable ≤ 2km |
HS2858/32 |
25kW |
Eight units of 2.5A/32kV |
25kVA/1/3/5kV |
200kV |
10kV cable ≤ 10km 35kV cable ≤ 4km |
Configuration Table of Voltage Endurance Devices for 110kV and Above Cables:
Product model name |
control cabinet |
Reactor (oil immersed) |
Excitation transformer (oil immersed) |
voltage divider |
Scope of Application |
HS2858/130 |
50kW |
Two 5A/130kV units |
50kVA/3/5kV |
150kV |
35kV cable ≤ 2km 110kV cable ≤ 2km |
HS2858/130 |
100kW |
5A/130kV four units |
100kVA/3/5/10kV |
220kV |
35kV cable ≤ 3km 110kV cable ≤ 3km |
HS2858/220 |
160kW |
Four 4A/220kV units |
160kVA/5/10kV |
160kV |
110kV cable ≤ 5km 220kV cable ≤ 3km |
HS2858/220 |
320kW |
Four 8A/220kV units |
320kVA/5/10kV |
320kV |