Immersion temperature sensor 1. Application field 1) Collecting temperature in water pipes and water tanks; 2) Used to control or limit the temperature of water flow; 3) Limit the return water temperature; 4) Control the temperature of domestic water

Immersion temperature sensor
1. Application Fields
1) Collect temperature data from water pipes and tanks;
2) Used to control or limit the temperature of water flow;
3) Limit the return water temperature;
4) Control the temperature of domestic water.
2. Technical parameters
Material/Signal 0~10V
Measurement range -10 ℃~120 ℃, 0 ℃~100 ℃, 0 ℃~70 ℃
Insertion length 100mm
Accuracy 0 ℃~70 ℃: ± 1K,-40℃~120℃:±1.4K
Response time 30 seconds
Protection level IP54
Power supply AC/DC24V
Wiring 3 wires
Sleeve has
3. Installation precautions
The installation position of the sensor is determined by its purpose
Used for water supply temperature control (heating fluid)
The pump is connected to the fluid, and the sensor is placed directly behind the pump
- Pump connection reflux, sensor placed 1.5m-2m behind the mixing valve
Used for return water temperature limitation
The sensor should be installed at the bend so that its immersion rod or protective package can face the direction of the fluid. The fluid at the temperature measurement point must
Fully mix, if the pump is connected to the return water, the temperature measurement point must be downstream of the pump, at least 1.5m away from the mixing point
Sensors should be installed in places that prevent signal lines from entering from the top
For all types of sensors, the immersion length should be at least 60mm
Sensors do not need to cover bonding materials
When installing the sensor, the threaded device or T-piece (G 189) should be welded onto the pipe