Intelligent multi-channel color paperless recorderAdopting a 32-bit high-end processor based on ARM core, high-speed information acquisition and processing are achieved, and a 128M large capacity flash memory chip can achieve ultra long time data storage.
Features
1. 5.6-inch 320X234 dot matrix TFT true color graphic LCD display, available in various styles such as 7-inch and 10 inch, with touch operation, CCFL backlight, clear image, vibrant colors, and wide viewing angle.
2. By using ARM based high-speed and high-performance microprocessors, it is possible to simultaneously detect, record, display, and alarm 8 signals.
3. Using a large capacity FLASH flash chip to store historical data, storing data for abnormal times, and losing data in case of power failure.
4. Fully isolated universal input, capable of inputting multiple signals without the need for hardware replacement, can be configured through instruments.
5. The displayed numerical range of the engineering quantity is wide, and the cumulative value can reach 4294967295.
6. Chinese menu configuration, display channel number, engineering unit, flow accumulation, temperature and pressure compensation, software password lock to protect user configuration security;
7. Alarm display, indicating the lower and lower limits, lower and upper limits, and upper and upper limits of each channel alarm simultaneously;
8. High display accuracy: The basic error for displaying numbers, curves, and bar charts is ± 0.5% FS.
9. Data transfer, using USB interface storage to backup or transfer historical data.
10. Standard serial communication interface: RS485 or RS232.
11. Can be connected to an external micro printer to meet the on-site printing needs of users.
12. Metal casing, allowing for use in harsh environments.
Main technical parameters:
1. Input signal: Thermocouples: standard thermocouples B, S, K, E, J, T, WRe, etc
Resistance: Standard thermal resistors Ptl0, Ptl00, Cu50, Cu50
Remote transmission pressure resistor 30-350 Ω
Current: Input resistance<250 Ω for O~1 0mA, 4-20mA, 0~20mA, etc
Voltage: 0-5V, 1-5V, mV, etc. Input impedance>250K Ω
Pulse signal: waveform rectangular, sine or triangular wave
Contact signal: electrical contact or input signal
2. Output signal: Current: 0-10mA (load resistance<250 Ω), 4-20mA (load resistance<500 Ω)
Voltage: 0-5V (load resistance ≥ 250K Ω), 1-5V (load resistance ≥ 250K Ω)
Feed output: DC24V, load < 30mA
Communication output: Interface method standard serial bidirectional communication interface: RS-485, RS-232C, RS-422
3. Measurement accuracy: ± 0.2% FS ± 1 word or ± 0.5% FS ± 1 word
4. Control/Alarm: 2-4 limit control or alarm output can be selected, indicated by LED
5. Temperature compensation: 0-50 ℃ digital temperature automatic compensation
6. Resolution: ± 1 word
7. Display range: -1999 to 9999 words
8. Display mode: -1999~9999 words measurement value display -1999~9999 constant value display
O. 56 inch or 0.8 inch high brightness LED digital display, LED working status display
9. Display content: Chinese menu, timed dynamic curve, historical curve recall, numbers, light bar, chart, status
10. Working environment: Temperature range of -10 ℃ to 50 ℃
11. Relative humidity: ≤ 85RH
12. Power consumption: ≤ 5W (powered by AC220V linear power supply)
13. Supply voltage: 220V (50HZ)
14. Size: (144 × 144 × 220mm) (width × depth × height)
Intelligent multi-channel color paperless recorderFault analysis and troubleshooting:
| Fault phenomenon | Root cause analysis | Treatment measures |
| The instrument does not work when powered on | 1》 Poor contact of power cord 2》 The power switch is not closed | Check the power supply |
| The signal display does not match the actual situation | 1》 Signal setting error in configuration 2》 Wiring error | 1》 Check configuration 2》 Check the signal line |
| Alarm output is abnormal | 1》 Alarm limit setting error 2》 The alarm point is shared by other channels | 1》 Reset the limit value 2》 Cancel other alarm points |
| Distribution output encountered problems | 1》 Incorrect wiring between transmitter and instrument 2》 Multiple transmitters are powered beyond the standard distribution of this instrument (distribution ≤ 30mA) 3》 Interference between digital and analog signals during power distribution | 1》 Correct wiring 2》 Use external power supply or customize large loads upon returning to the factory 3》 Use independent power supply or factory customization |
| USB transfer failed | 1》 Incorrect start and end time settings 2》 The USB drive format is incorrect 3》 USB drive incompatible 4》 Insufficient remaining space on the USB drive
5》 Incorrect operation during backup process | 1》 Set the time correctly 2》 Format USB drive to FET32 3》 Use genuine and compatible USB drives 4》 Use a larger capacity USB drive or clean up excess files on the USB drive 5》 Correct operation |
| No data or abnormal display in USB file transfer | 1》 No data available for the time period selected by the user 2》 The user has changed the system time 3》 The user has changed the signal type 4》 The record interval set by the user is too large, but the backup time is very short 5》 USB drive incompatible 6》 The data time period is too long, exceeding the large reading time domain of the upper computer software | 1》 Choose a time with data segments 2》 Erase the data area once 3》 No impact on data recording 4》 Set the recording interval to be smaller or the backup time to be longer 5》 Use genuine and compatible USB drives 6》 Set the time period for data backup to be smaller, and backup in segments and batches |
| Communication is not available | 1》 The communication cable is not properly connected 2》 Communication parameter setting error 3》 Communication serial port setting error | 1》 Connect the communication cable correctly 2》 Communication parameter settings between recorder and PC* 3》 Set the correct communication COM port (confirm that it is not occupied by other programs) |