KYN28A-12 High Voltage Removable Switch Cabinet

NegotiableUpdate on 02/04
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
KYN28A-12 High Voltage Removable Switch Cabinet
Product Details
summary:
KYN28A-12 AC Metal Armored Removable Switchgear is a complete set of indoor switchgear for three-phase AC and 50Hz, rated voltage 3-12kV, single busbar and single busbar segmented system. It is mainly used for receiving and distributing electrical energy in power plants, substations, residential distribution, and distribution rooms of industrial and mining enterprises. It can also be used for starting control of high-voltage motors, and can achieve control, protection, and detection of circuits. The switchgear can be equipped with imported brand circuit breakers such as VD4, EV12, HVX, AV3, as well as domestic brand circuit breakers such as VS1, VEP, VBG, ZN73A.
This switchgear complies with standards such as GB3906-2006 "3.6~40.5kV AC Metal Enclosed Switchgear and Control Equipment", GB/T11022 "Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards", IEC62271:2000 "AC Metal Enclosed Switchgear and Control Equipment for Rated Voltage Above 1kV and Below 52kV", DL/T404 "Technical Requirements for Ordering Indoor AC High Voltage Switchgear", etc.
Main technical parameters
Rated voltage (kV): 3.6, 7.2, 12
Rated current (A): 630, 1250, 1600, 2000, 2500, 3150, 4000
Rated frequency (Hz): 50
1-minute power frequency withstand voltage (kV): phase to phase, relative to ground 24,32,42
Isolation fracture 24, 32, 48
Lightning impulse withstand voltage (kV): phase to phase, relative to ground 40, 60, 75
Isolation fracture surfaces 46, 70, 85
Rated short-time withstand current (4s) (kA): 20, 25, 31.5, 40
Rated peak withstand current (kA): 50, 63, 80, 100
Rated short-circuit breaking current (kA): 20, 25, 31.5, 40
Rated short-circuit closing current (kA): 50, 63, 80, 100
Operation sequence: Split -0.3s-Split -180s-Split
Control circuit voltage (V): DC 110, 220
Communication 110, 220
Shell protection level: The shell is IP4X
The circuit breaker room door is opened to IP2X
Dimensions (width * depth * height) (mm): 800 * 1500 (1660) * 2300
1000*1500(1660)*2300
Weight (circuit breaker cabinet):<800kg