Design features
Multi functional temperature transmitter/temperature switch
Multiple clamping units for process connection
The clamp block is applied to pipes Ø 4... 57mm
The clamp ring is applied to pipelines Ø 10... 300mm
The clamp hook is used for pipes Ø 4... 17.2mm
Sanitary temperature measurement for pipe diameters ranging from 4 to 300mm
■ Measurement system acquisition
High precision and fast response
Easy to install
No need for welding, no need to interrupt the production process
No need for additional isolation
■ Insertable measuring components can be calibrated
Sanitary design and structural design comply with EHEDG standards
4-digit LED display, capable of 180 ° reverse display
The indicator module can rotate freely up to 300 °
Process temperature range -40 ℃ to 150 ℃
Output signal 4... 20mA, two-wire technology
■ Convenient on-site programming
The transmitter and switch outputs are electrically isolated
optional
Parameter adjustment can be made through COMLINE.SPC software
Two floating switch contacts
The switch contact has a high switching current (1A)
The verification certificate complies with DINEN10204-3.1
The electrical connection can rotate 300 °
LABOM type temperature switch manufacturer
Application field
Food industry
Pharmaceutical industry
Biochemical technology
Shell design
Design seamless sanitary shell, fully encapsulated
electronic component
Material: Stainless steel 1.4301 (304),
Display module Macrolon
Protection level IP67, compliant with DINEN60529
Electrical connections Circular connector M12, 4-pin
Circular connector M12, 8-pin 1
When equipped with a switch option, it is necessary to
Temperature measuring element
Measure the insertion of stainless steel Ø 6mm, threaded connection with the connector, and subjected to spring tension.
The measurement insertion part can be recalibrated or replaced. The installation method remains unchanged. The measuring unit is made of silver and isolated by plastic insertion components.
Measurement of resistance Pt100, three wire thin layer technology
temperature range
Environmental temperature -20 ℃... 85 ℃
Process temperature -40 ℃... 150 ℃
Allowable storage temperature -40 ℃... 100 ℃
Other temperature ranges are based on customer requirements.
Pipe clamp
Material: heat-resistant high-performance plastic, integrated isolation system
Protection level IP65, compliant with DINEN60529
Nominal size of pipeline
Applicable to all standard nominal pipelines. Please refer to the selection table for detailed dimensions.
instruction
Type 4-digit number, red 7-segment
LED on-site indication
Digital display height 8.5mm
Numbers with resolutions ranging from 9999 to 9999
The direction can be rotated 300 degrees, and when installed in reverse,
Digital display can be reversed 180 °
instructions? measured value
Measurement unit
Operation menu
The decimal point is automatically set according to the measurement range/unit
Z can be set in 3 positions or manually set in positions 0... 3
Temperature and units can be alternately displayed on the screen through manual buttons or by pressing cycles (cycles can be set)
Measurement units ℃, ℉, K, mA can be set
measurement range
The measurement range parameters can be set between -40... 150 ℃, with a small range span of 25K
output signal
Output signal 4... 20mA, two-wire technology loading communication signal response characteristics temperature linearity
Current range 3.8... 20.5A
Resolution 0.3A
Current limit ≤ 21mA
Load ≤ (U-12V)/21mA (Ohm)
Switch delay<5s
auxiliary power supply
Nominal voltage 24VDC
Scope of work: 12... 30VDC
Integrated voltage reverse protection
precision
transmitter
Linear error*
<0.2K or 0.08% measurement range
Temperature effect Tu1<0.1%/10K
Auxiliary power supply impact<0.005% measurement range
Load impact ≤± 0.02%/100 Ω
1Tu=ambient temperature
parameter |
numerical value |
|
unit |
℃, ℉, K,mA |
|
temperature calibration |
Range lower limit value/Range upper limit value |
|
Z small/Z large value |
Resettable between the upper and lower limits of the range |
|
Measurement value display time |
1.0…99.9 s |
|
Unit display time |
0.0…99.9 s |
|
Display Rotation |
0 ° (normal installation)/180 ° (reverse installation) |
|
decimal point |
Automatic, can manually set the decimal point position from 0 to 3 |
|
switching method |
Lag type-Open it
-Close
|
Window style - Open
-Close
|
switch point |
Between the upper limit of the measurement range and the reset point |
|
Reset point |
Between the measurement range next week and the switch point |
|
ON delay |
0.0…999.9 s |
|
OFF delay |
0.0…999.9 s |
|