Product Introduction:
Product Features
All imported optical components with stable performance
5-meter high-temperature detection pool, achieving high-resolution and high-precision detection
Spectral multi line scanning can eliminate interference from dust, tar, and background gas
Imported sampling unit, 200 ° C heat tracing
Regular calibration, low cost of use
Typical Applications
• Denitrification and ammonia injection optimization process, hydrogen chloride and hydrogen fluoride process control sampling and testing
Online ammonia escape, hydrogen chloride, and hydrogen fluoride comparison monitoring
Diesel engine ammonia injection detection
• Laboratory gas analysis

Laser gas analyzer portable flue gas analysis system gas detection
| performance parameters | |||||||
| model | gas | Detection range | resolution | response time | drift | ||
| pLAS-100 | NH3 | 0-100mg/m3 | 0.1mg/m3 | ≤15s | ≤1%FS 7d | ||
| pLAS-200 | HCL | 0-100mg/m3 | 0.1mg/m3 | ≤15s | ≤1%FS 7d | ||
| pLAS-300 | HF | 0-100mg/m3 | 0.1mg/m3 | ≤15s | ≤1%FS 7d | ||
| Electrical parameters | |||||||
| warm-up time | 60min | digital output | RS485 | data storage | Configure USB 2.0 interface | ||
| power supply | AC220V | power | <0.8kw | ||||
| environmental parameters | |||||||
| Sample humidity | 0-99%RH | Sample gas temperature | ≤600℃ | Sample gas pressure | Atmospheric pressure ± 5kPa | ||
| sampling flow | 2-3L/min | ambient temperature | -30-55℃ | environmental stress | 70kPa-120kPa | ||
| mechanical parameters | |||||||
| External dimensions of analyzer host | 210(W)*460(L)*340(H)mm | weight | 18kg | ||||
| Specification of sample gas inlet connector | 6mm stainless steel card sleeve joint | Specification of sample gas outlet connector | Φ6mm PVDF connector | ||||
Note:1. Customization of other gas measurements is available; 2. Customizable multi-component gas measurement; 3. The detection range can be customized according to customer requirements