OMP-APK25+M60-2 primary power lightning arrester manufacturer wholesale

NegotiableUpdate on 04/09
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Product corresponding parameters: Installation and usage scenario: Distribution cabinet/box Equipment box Lightning arrester category: Power supply nominal working voltage (Un): 380V Maximum continuous operating voltage (Uc): 385V Lightning impulse current 10/350 μ s: 25KA Interface type: Terminal block Installation method: Series connection
Product Details
OMRDON 25KAI Surge Protection Device (SPD) (also known as lightning arrester, surge protector, overvoltage protector) has high lightning current capability and is suitable for electromagnetic pulse (EMP) protection generated by lightning strikes in TN-S, TN-C-S, TT, IT and other power supply systems with AC 380V (50Hz/60Hz) and below. It is used at the junction of LPZ OA or LPZB area and LPZ1 area in lightning strike areas
Precautions for installation of lightning arrester:
1. This SPD should be installed in parallel. Generally, only one of the two terminals needs to be connected, or a dual connection method (Kevin connection method) can be used. The connecting wire should be firm and reliable, and should be short, thick, and straight.
2. Please connect according to the installation diagram during installation, where L1, L2, and L3 are phase wires, N is neutral wire, and PE is ground wire. Do not connect them incorrectly. After installation, close the automatic circuit breaker (fuse) switch.
3. It is recommended to connect a fuse or automatic circuit breaker in series at the front end of the SPD. Ensure to avoid short circuits causing fires after the deterioration of lightning arresters.
4. Remember not to carry out live work, the power must be cut off before installation, and live operation is strictly prohibited.
5. The grounding must be good and comply with relevant national lightning protection regulations
6. The equipment needs to be regularly inspected and replaced immediately after product degradation.
Product application and installation location:
The OMRDON Class I series surge protectors are suitable for the interface between LPZOA or LPZOB areas and LPZ1 areas in lightning strike zones. They are usually installed in parallel at the main distribution cabinet or floor distribution cabinet of the buried conduit incoming low-voltage household end.
Typical applications: Mobile communication base stations, microwave communication bureaus/stations, telecommunications rooms, industrial plants and mines, civil aviation, finance, securities and other power systems, such as various distribution stations, distribution rooms, distribution cabinets, switch boxes and other important and vulnerable equipment to lightning strikes.

name

T1Class surge protector

model

OMP-APK25+M60-2

SPDport

One port

Experimental level (based onIEC61643-1

Class I

SPDcategory

Wide wave type

protected mode

L-PEN-PE

Rated working voltage(Un)

220V/380V

Maximum continuous operating voltage(Uc)

385V 50Hz/60Hz

Voltage protection level(Up) (1.2/50μs)

≤2.2kV

Pulse current resistance(In)

25kA(8/20μs)

Lightning surge current (IMP)

25KA(10/350μs)

response time (Ta)

≤25ns

Continuous flow interruption capability

500Arms

(AC50~60Hz 255Vrms) If

insulation resistance

100MΩ

Definition of Remote Communication

NC Normally closed,COM Public points,NO Normally Open

Cross sectional area of remote signaling terminal wiring

maximum1.5mm2single strand/Multi strand soft copper core wire

Connecting wire cross-section(L/N)

≥10mm2

Connecting the cross-section of the grounding wire(PE)

≥16mm2

(Phase line cross-sectional areaS≤16mm2When using the ground wireS; Phase line cross-sectional area16mm2≤S≤35mm2When using the ground wire16mm2; Phase line cross-sectional areaS≥35mm2When the ground wire is requiredS/2 Based onGB500542.2.9article)

Selection of backup protection circuit breakers

Dtype63A-125A/35KA

working environment

-40℃~+85℃

relative humidity

≤95%

install

35mmStandard electrical guide rail

housing material

Enhance flame retardancyPBT

IP protection level

IP20

Test Basis

GB18802.1TheIEC61643-1

Item Number

800102

25KA电源防雷器