Welcome Customer !

Membership

Help

Guangzhou Chuangxuanli Information Technology Co., Ltd
Custom manufacturer

Main Products:

ybzhan>Products

Guangzhou Chuangxuanli Information Technology Co., Ltd

  • E-mail

    13928740423@139.com

  • Phone

    13556075810,15815976881,13760787316

  • Address

    628, 6th Floor, Zonghua Building, No. 2 Gongye 1st Road, Dashi Street, Panyu District, Guangzhou City, Guangdong Province

Contact Now

Shantak ARRAY 3A3 series (15KVA~150KVA)

NegotiableUpdate on 10/25
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Product User Manual (click to download) Excellent electrical performance, low input harmonic current, high output voltage accuracy, strong overload capacity: 110-130% load can be overloaded for 10 minutes

Product Details


Product User Manual (Click to Download)




Product features

Excellent electrical performance
Low input harmonic current:<5%
High output voltage accuracy:<2%
Strong overload capacity: 110-130% of the load can be overloaded for 10 minutes, and 130-150% of the load can be overloaded for 1 minute
High charging current: 4.5A (per module)
Supports variable frequency mode with 50Hz input and 60Hz output, or 60Hz input and 50Hz output


Fully digital control
The 3A3 UPS module adopts TI's most advanced DSP as the central controller, which has powerful computing power and can replace most of the control functions completed by hardware in traditional UPS with software. This not only greatly improves reliability and accuracy, but also facilitates upgrading and maintenance.

Intelligent charging method

3A3 UPS adopts an advanced two-stage three-stage charging method. The first stage is high current constant current charging, which quickly recharges about 90% of the battery; The second stage of pulsating charging can homogenize battery characteristics and fully charge the battery; The third stage maintains constant voltage to ensure that the power is not lost. This can effectively balance the goals of fast charging and extending battery life, saving users battery expenses.

The highest power density in the industry
A 3A3 UPS module has a volume of 440 × 700 × 131mm (3U), and a standard 2-meter-high UPS cabinet can accommodate up to 10 UPS modules with a total capacity of 150KVA. The distribution panel is also included, and a battery cabinet of the same size as the UPS cabinet can be used to form a complete UPS power supply system. Due to the use of standard cabinets for both UPS cabinets and battery cabinets, which are consistent with the load equipment cabinets in most computer rooms, they can be placed side by side with the load without the need for a dedicated UPS distribution room. This not only looks beautiful but also maximizes installation space savings for customers.

N+X wireless parallel redundancy
By adopting advanced wireless parallel control technology, compared to wired parallel connection, it reduces single point of failure (even if there is a signal line fault in parallel during steady-state operation, it can still work normally), and further improves reliability.

Parallel shared battery
The 3A3 UPS adopts a dual battery input structure and advanced control strategy, and the parallel system completely shares the same set of batteries, greatly saving battery costs.

Flexible system configuration
3A3 UPS adopts modular design and easy to plug function, consisting of UPS module, communication module, distribution panel, some optional components, and cabinet. The UPS module and communication module can be replaced online without affecting the normal operation of other parts. Newly added modules can be added to the system without any calibration action, making expansion and maintenance very convenient. Users can choose different module numbers according to their needs to construct a UPS system with a suitable capacity between 15KVA and 120KVA, and the configuration is very flexible. For future device expansion, simply inserting a few more UPS modules can easily complete it. If users leave a margin for switches and power lines when installing for the first time, they can expand the capacity of UPS by purchasing UPS modules when the load increases in the future, completely avoiding the disadvantage of excessive initial equipment investment in traditional UPS. This truly achieves "growing while investing" and saves valuable funds for users.

Optimal power supply system topology
3A3 UPS integrates the advantages of centralized and decentralized power supply topologies and introduces the concept of regional power supply in its design. If several areas are separated in a large data center, each area is equipped with one or two (redundant backup) 3A3 UPS power supply systems, which are directly placed next to the load in that area and powered through the distribution panel on the cabinet. In this way, each region has centralized power supply and management, while the regions have independent decentralized power supply and independent wiring. The 3A3 UPS power supply method has the advantages of decentralized "flexible configuration, allowing gradual investment, and not easily causing large-scale paralysis", as well as centralized "easy management".

Humanized operating interface and comprehensive power management software
The parallel system adopts a large Chinese LCD screen as the operating interface, making operation and information reading clear at a glance. Paired with the latest monitoring software WINPOWER2003, power management has become easier. If equipped with WEBPOWER and SNMP cards, remote monitoring can be achieved more effectively.

Extremely high system availability

If the UPS has more than two redundant UPS modules, the availability of the UPS can reach over 99.999%, and the MTBF (Mean Time Between Failures) can reach over 15 million hours.

Minimum downtime for maintenance
If the number of faulty UPS modules is less than or equal to the number of redundant UPS modules, the faulty UPS module can be replaced online without affecting the operation of other modules. In this case, the downtime for maintenance is zero; If the number of faulty UPS modules is greater than the number of redundant UPS modules, the downtime for maintenance will not exceed 5 minutes due to the replacement of UPS modules.

Specification parameter table
model
ARRAY series cabinets
Input wiring
Three phase+neutral wire+ground wire
input voltage
124-300VAC (phase voltage); 214-520VAC (line voltage)
input frequency
40-70Hz
Input power factor
≥ 0.99
Input bypass voltage range
187-253VAC (phase voltage); 323-437VAC (line voltage)
Output wiring
Three phase+neutral wire+ground wire
output voltage
380×(1±1%)VAC
output frequency
Synchronized with the input mains power, when the mains power frequency exceeds the range, the output frequency is 50 × (1 ± 0.5%) Hz (mains power mode);
50 × (1 ± 0.5%) Hz (battery mode)
Output power factor
0.9
Output overload time
≥ 10 minutes (110% < load ≤ 130%)
Output UPS efficiency
+192VDC/+204VDC/+216VDC/+224VDC/+240VDC
Number of single-sided battery cells
16/17/18/19/20
Positive battery voltage
+192VDC/+204VDC/+216VDC/+224VDC/+240VDC
Positive battery charging current
3.5A x number of modules
Negative battery voltage
-192VDC/-204VDC/-216VDC/-224VDC/-240VDC
Negative battery charging current
3.5A x number of modules
noise
< 62dB
ambient temperature
0-40℃
ambient humidity
20-90%
size
2.0-meter 60kVA downstream cabinet: 600 × 1050 × 2030mm 200kg
2.0-meter 90kVA outgoing cabinet: 600 × 1050 × 2030mm 230mm
2.0-meter 90kVA outgoing cabinet: 600 × 1050 × 2030mm 230mm
2.0-meter 120kVA outgoing cabinet: 600 × 1050 × 2030mm 265mm
2.0-meter 120kVA outgoing cabinet: 600 × 1050 × 2030mm 265mm
2.0-meter 150kVA downstream cabinet: 600 × 1050 × 2030mm 275mm
Distribution panel: 483 × 194 × 131mm
UPS module: 440 × 707 × 131mm
weight
2.0-meter 60kVA downstream cabinet: 200kg
2.0-meter 90kVA outgoing cabinet: 230kg
2.0-meter 90kVA outgoing cabinet: 230kg
2.0-meter 120kVA outgoing cabinet: 265kg
2.0-meter 120kVA outgoing cabinet: 265kg
2.0-meter 150kVA downstream cabinet: 275kg
Distribution panel: 9kg
UPS module: 35kg
Customer Service and Support
Three year warranty/24-hour free service hotline/national warranty/online technical service support