| model | Impulse current (KA) (10/350 μ s) | Nominal discharge current (KA) (8/20 μ s) | Maximum continuous operating voltage Uc (V) | Response time (ns) ≤ | Protection level Up (KV) ≤ | Wiring mode |
| GS-I/15/60 | 15 | 60 | 220-1500V (AC/DC selected based on system voltage) | ≤100 | 2.0 | 3P/3P+N |
| GS-I/25/80 | 25 | 80 | ≤100 | 2.2 | ||
| GS-I/35/100 | 35 | 100 | ≤100 | 2.5 | ||
| GS-I/50/150 | 50 | 150 | ≤100 | 3.0 |
1. A multi stranded copper wire with a power connection wire of not less than 6mm2, and a multi stranded copper wire with a grounding connection wire of not less than 10mm2. The connecting wire should be as short, straight, and thick as possible.
2. The front end of the lightning arrester should be connected in series with suitable backup protectors, fuses, or air switches.
1. During installation, the power must be disconnected and live operation is strictly prohibited. The connecting wires must meet the requirements.
2. After installation, insert the lightning protection module into place and check if it works properly.
3. The lightning arrester does not require special maintenance, it only needs to be regularly checked for loose connections and normal status indicators.