Transformer core clamp grounding monitoring deviceUsed to monitor the grounding fault current of transformer iron cores and clamps, it can achieve continuous and online monitoring of the grounding current of the iron core. Through monitoring, the insulation condition of the equipment can be monitored in real time, and faults such as internal insulation moisture or damage, multi-point grounding of the iron core, foreign objects in the box, and oil sludge deposition in the oil tank can be detected in a timely manner. Early prevention and handling of accidents. More importantly, it can provide reliable data basis for the condition maintenance of such equipment.
Its working principle is:
The system uses high-precision through type sensors to convert the grounding current signal on the iron core and clamp into a voltage signal. The voltage signal enters the signal conditioning circuit, which automatically switches the range according to the voltage magnitude. Finally, it enters the signal measurement board with DSP as the processing core, which uses a high-performance 32-bit digital processing chip DSP as the core processor. The grounding current of the iron core and clamping components is accompanied by on-site interference signals, and these interference signals must be eliminated first when calculating. The traditional method is to use analog filters to remove interference signals, but analog filters are easily affected by environmental temperature and humidity, and are prone to zero drift and other phenomena over time, thus introducing new "interference". And the powerful digital computing function of DSP can use digital filtering algorithms instead of the original analog filtering algorithms. The digital filtering algorithm is not affected by environmental factors such as temperature and humidity, and has zero drift, which can solve various problems caused by analog filters. The signal measurement board calculates the grounding current of the iron core and clamping components and uploads it to the interval level monitoring IED through a digital bus. The interval layer IED adopts a unified embedded platform to implement functions such as analysis and judgment, alarm, and remote data transmission. By monitoring the magnitude of the grounding current of the iron core during operation, it is automatically determined whether the transformer iron core is not grounded or has multiple grounding points, thereby preventing the formation of floating potential and a series of faults caused by local overheating of the iron core, ensuring the safe operation of power transformers.

Adopting high-precision active zero magnetic flux sensors, intelligent selection of conditioning circuits and amplification factors based on the measured current size effectively improves measurement accuracy
The technical parameters of this device meet or exceed the following standards and regulations: "Inspection Specification for Substation Online Monitoring Devices Part 1: General Inspection Specification" Q/GDW 540.1-2010
1. Working environment
Working voltage: AC 220V ± 10%, 50Hz
Working environment temperature: -40 ℃~120 ℃
Power consumption:<5W at rated voltage
Working environment humidity: ≤ 95%
2. Monitoring parameter indicators
Measurement current range: 1mA~10A Accuracy: ± 1% or ± 1mA whichever is greater
3. Communication parameters
通信接口: RS485,2400,N,8,1
Communication protocol: MODBUS-RTU
construction method
1) The iron core grounding copper bar passes through the zero flux transformer, which is fixed to the transformer housing or independently installed on a bracket through a bracket and related insulation materials.
2) The transformer is connected to the iron core grounding monitoring device through a 4-core cable, and the iron core grounding monitoring device is installed on a separate bracket attached to the transformer.