1 Product Introduction
XSLC8The temperature inspection instrument adopts imported high-quality wiring terminals and an aluminum alloy shell. Each input channel is equipped with surge and overvoltage protection. Each channel of the transmission output is isolated, and strict anti-interference design is selected to suppress fast pulse group interference and other electromagnetic interference generated by relays, contactors, etc. on site. apply to2~8Point temperature detection, alarm, and transmission output. Can be matched with various thermal resistors and thermocouples.
II Product Features
1. Basic error less than0.2%F·S, display range-1999~9999The resolution of the thermistor signal display is0.1℃,
Thermocouple signals can be selected through parameter selection1℃ or0.1℃. The basic error of the transmission output is less than ±0.5%F·S;
2. Each channel independently sets the input signal type2Point alarm value;
3. Each channel independently sets a digital filtering time constant to improve display stability;
4. Unused channels can be closed at will;
5. Display color: Channel displayRed ", measurement shows" green ".
3、 Selection
content |
Code Description |
||||||||
XSLC- |
0.2Level measurement accuracy; Measurement and control speed(0.1X number of channels) |
||||||||
Channel |
08 |
8Road input |
|||||||
External dimensions |
160×80×124 horizontal type Hole size:152×76 |
||||||||
Panel specifications |
2positionLED(Channel number display)+ 4positionLED(Measurement value display) |
||||||||
Input signal |
All channels are universal inputs, and the input signal is set by parameters: Thermal resistance(Pt100/Cu100/Cu50/BA1/BA2/G53) Thermocouple(K/S/R/B/N/E/J/T) Direct current((4-20)mA/(0-10)mA/(0-20)mA) DC voltage((0-5)V、 (1-5)V)Signal or(mVSignal(+100 ~ -100)mV) |
||||||||
call the police |
2Click on the public alarm. (Relay output,250V AC/3A, resistive load) |
||||||||
communication(Communication speed:2400、4800、9600、19200、38400、57600)(Mailing address:0~99) |
S1 |
RS232Interface, selected through parameter settingsTC ASCII orModbus-RTUagreement |
|||||||
S2 |
RS485Interface, selected through parameter settingsTC ASCII orModbus-RTUagreement |
||||||||
|
Transducer(Optional) (Not compatible with communication at the same time. Resolution:1/3000Load capacity:600Ω)
|
A1 |
Current output(4-20)mA、 (0-20)mA、 (0-10)mA |
|||||||
A2 |
Voltage output(0-5)V、 (1-5)V |
||||||||
Power specifications |
V0 |
100-240V AC 50/60 Hz |
|||||||