YD9810The type axis vibration transmitter is equipped with an eddy current sensor to form a system (note1),It can measure shaft vibration, runout, etc., and monitor the increase in vibration caused by rotor imbalance, misalignment, and loose parts. Mainly used to monitor the radial vibration of rotating machinery rotors, provide real-time total vibration of rotors, protect rotating machinery and output analog current, alarm, and shutdown signals, which can be easily connected withDCSThePLCSystem connection.
Working power supply:24VDC±10%
Input signal: Receive eddy current sensor probe signal, sensitivity8.0V/mm
quantity Cheng:0~500um(Peak to Peak
Current output:4~20mA,Output load ≤350Ω
Measurement error:《1%full scale
Alarm point setting:0~100%Full scale, accuracy ±1%
Relay sealing: epoxy resin, node capacityDC30V/5AorAC220V/5A,Single blade double throw
Alarm reset mode: manual or automatic
Slow output: The output of the original signal,8.0V/mm,output impedance10KΩ
Temperature range:
Run time:0~+65℃;
During storage: -30℃~+80℃
Relative temperature: to95%,Not condensing
Overall dimensions:90x120x75mm
Installation size:80x90mm
1Installation of transmitter
The transmitter can be fixed in two ways: rail fixing or screw fixing
Rail fixation:35mmStandard guide rail, simply insert the transmitter directly into the guide rail to fix it.
Screw fixation: open at an appropriate position on site4A hole, with an installation size of80x90mm,Aperture:4-q4.5mm.

35mmRail fixed transmitter
The transmitter can be installed in the control room or on-site. But if the on-site environment is harsh, it is recommended that the user install the transmitter in an explosion-proof installation box (note2)Alternatively, a guide rail installation can be used in the control room, and the terminal block on the transmitter can be directly pulled out. After fixing the cable, it can be inserted into the terminal block.
note2:In harsh on-site environments, users can order explosion-proof installation boxes from the manufacturer. When selecting an explosion-proof installation box, first fix the transmitter in the explosion-proof box, then position it in the appropriate position on site according to the installation size, and then fix the box body with screws.
2Installation of sensors
The installation of sensors includes the installation of the preamplifier (note3)For the installation of probes and extension cables, please refer to the subsequent section on eddy current sensors for specific installation requirements.
note3:If the transmitter has integrated a preamplifier function, there is no need to install a preamplifier;
wiring
After all the components are installed and fixed, the entire measurement system can be connected. Connect according to the wiring diagram.
Multimeter measurementSensor Gap(+At both ends, the gap voltage can be measured
Note:
φ8mmProbe thread specificationM10x1,Recommended installation room
gap1.5mmLeft and right, the gap voltage is about -10V;
Φ5mmProbe thread specificationM8x1orM10X1,push
Recommended installation gap0.75mmLeft and right, the gap voltage is about -6V;

Schematic diagram of YD9810 integrated shaft vibration transmitter wiring
The gap voltage can be measured at both ends of Signal In on the transmitter