YSJ-17001 Pressure ControllerCan be used for neutral or corrosive gases and liquid media. The setting value range is adjustable, with an adjustment range of 0.02~42Mpa. The switching difference is not adjustable Pressure controllers include a wide range of products, including differential pressure controllers, pressure switches, differential pressure switches, pressure transmitters, differential pressure transmitters, wind pressure switches, and wind pressure transmitters,
The controller has a small volume, light weight, and is suitable for the requirements of dense installation in aircraft, ships, and vehicles. It also has the advantages of adjusting action pressure, convenient control, accurate and reliable control, and can be directly installed in on-site pipelines.
YSJ-17001 Pressure ControllerFunctional parameters:
1. Select the controller so that the predetermined set value is located in the middle of the controller's set value adjustment range. Generally, it ranges from 20% to 80% of the adjustment range.
2. When the controller is to be installed outdoors, sufficient protection should be provided to avoid drastic changes in ambient temperature, direct sunlight radiation, and the infiltration of corrosive gases or water.
3. When installing cables, the appropriate outer diameter of the cable should be selected, and the tightening nut at the cable entry point should be tightened to prevent the cable from loosening and to prevent the infiltration of water or dust.
4. For controlled liquid media with pressure peaks and pulse pressures, a pressure shock damper can be installed on the interface of the controller to eliminate adverse effects.
5. The on/off current cannot exceed the rated value.
6. When installing (or disassembling) the controller, special attention should be paid to:
1) The flat part of the sensor must be clamped with a wrench during installation (or disassembly) to prevent relative rotation between the sensor and the switch housing.
2) When the sensor interface is internally threaded, the depth of the pipe joint screwed into the sensor should not exceed 12mm.