E-mail
1095143601@qq.com
-
Phone
18936740760
-
Address
No. 358 Shenhua Avenue, Jinhu County Industrial Park
Jiangsu Hengke Measurement and Control Instrument Co., Ltd
1095143601@qq.com
18936740760
No. 358 Shenhua Avenue, Jinhu County Industrial Park
Our company acts as an agent for the complete range of Yokogawa EJA transmitters, including EJA110A differential pressure transmitter, EJA430A pressure transmitter, EJA120A micro differential pressure transmitter, Yokogawa EJA130A high static pressure differential pressure transmitter, EJA310A pressure transmitter, EJA440A high static pressure transmitter, Yokogawa EJA210A/EJA220A flange transmitter, EJA510A/530A absolute pressure transmitter, EJA118 diaphragm sealed differential pressure transmitter, EJA438 diaphragm sealed pressure transmitter, and EJA115 micro flow transmitter.
Specification of EJA110A
|
EJA110A differential pressure transmitter |
||||
L membrane box |
M membrane box |
H membrane box |
V-film box |
||
measurement range |
-10~10kPa |
100~100kPa |
500~500kPa |
-0.5~14MPa |
|
Measurement range |
0.5~10kPa |
1~100kPa |
5~500kPa |
0.14~14MPa |
|
precision |
±0.075% |
±0.065% |
±0.065% |
±0.065% |
|
Protection level |
IP67,NEMA 4X, And JIS C0920 immersion proof type |
||||
Explosion proof specifications |
FM,CENELEC ATEX,CSA,IECEx |
||||
output signal |
4~20mA DC, FOUNDATION fieldbus or PROFIBUS PA two-wire digital communication |
||||
power supply |
BRAN and HART: 10.5~42V DC (intrinsic safety type: 10.5~30V DC) |
||||
ambient temperature |
-40~85℃ (-40~185℉) (普通型) |
||||
process temperature |
-40~120℃ (-40~248℉) (普通型) |
||||
Great work pressure |
16MPa(2300psi) |
||||
install |
2-inch pipe installation |
||||
Material of liquid receiving components |
bellows |
SUS316L (diaphragm: Hastelloy C-276), |
|||
Container flange |
SUS316, Hastelloy C-276, Monel |
||||
shell |
Aluminum alloy or SUS316 stainless steel (optional) |
||||
Specification of EJA120A
|
EJA120A Micro Differential Pressure Transmitter |
|
E-membrane box | ||
measurement range |
-1~1kPa(-4~4inH2O) |
|
Measurement range |
0.1~1kPa(0.4~4inH2O) |
|
precision |
±0.2% |
|
Protection level |
IP67,NEMA 4X, And JIS C0920 immersion proof type |
|
Explosion proof specifications |
FM,CENELEC ATEX,CSA,IECEx |
|
output signal |
4~20mA DC or FOUNDATION fieldbus or PROFIBUS PA two-wire digital communication |
|
power supply |
BRAN and HART: 10.5~42V DC (intrinsic safety type: 10.5~30V DC) |
|
ambient temperature |
-25~80℃(-13~176℉) |
|
process temperature |
-25~80℃(-13~176℉) |
|
Great work pressure |
50kPa (7.25psi) |
|
install |
2-inch pipe installation |
|
Material of liquid receiving components |
bellows |
SUS316L (diaphragm: Hastelloy C-276) |
Container flange |
SUS316 |
|
shell |
Aluminum alloy or SUS316 stainless steel (optional) |
|
Specification of EJA430A
|
|
EJA430A pressure transmitter |
||
A membrane box |
B membrane box |
||
measurement range |
-0.1~3MPa |
-0.1~14MPa |
|
Measurement range |
0.03~3MPa |
0.14~14MPa |
|
precision |
±0.065% |
±0.065% |
|
Protection level |
IP67,NEMA 4X, And JIS C0920 immersion proof type |
||
Explosion proof specifications |
FM,CENELEC ATEX,CSA,IECEx |
||
output signal |
4~20mA DC or FOUNDATION fieldbus or PROFIBUS PA two-wire digital communication |
||
power supply |
BRAN and HART: 10.5~42V DC (intrinsic safety type: 10.5~30V DC) |
||
ambient temperature |
-40~85℃ (-40~185℉) (普通型) |
||
process temperature |
-40~120℃ (-40~248℉) (普通型) |
||
High overvoltage |
4.5MPa (645psig) |
21MPa (3000psig) |
|
install |
2-inch pipe installation |
||
Material of liquid receiving components |
bellows |
SUS316L (diaphragm: Hastelloy C-276), |
|
Container flange |
SUS316, Hastelloy C-276, Monel |
||
shell |
Aluminum alloy or SUS316 stainless steel (optional) |
||