I. Overview:
ZK-3CThe three-phase thyristor voltage regulating trigger is manufactured using integrated circuit device technology, which has stable technical performance, strong resistance, and reliable quality. The dashboard is equipped with“Output settings'Power adjustment knob (dial)“automatic/manual'Switch button and“pressure regulation/Adjusting skills'Two types of trigger thyristor working mode buttons, built-in6The digital function switch is designed to meet the needs of users for control systems, and is small in size and light in weight, making it an ideal actuator for various types of three-phase electric heating automatic temperature control systems.
2、 Technical indicators:
1Input signal:DC0-10mA,input impedance800Ohm. According to user needs, additional services can be providedDC4-20mA,DC1-5VWait. )
2Output signal: Three phase pulse output, with positive pulses output for each phase.
pulse amplitude≥4V(20load);
pulse width≥0.2ms:
Phase shift range≥170;
Power regulation range0-100%Linear adjustment.
3Equipped with controllable silicon:KPpipe(one-way)1000Abelow.
KSpipe(bidirectional)500Abelow.
4Power supply:-380V±10%,50HZ.
5Working environment:Temperature<50℃,Relative humidity<85%.
6Weight:≤3kg.
7Power consumption:about6W.
3、 Panel layout instructions:
1、“%'------The symbol window displays the output quantity ratio;
2、“Output regulation'------Set output power;
3、“pressure regulation/Power adjustment button'------Select the triggering thyristor working mode;
4、“manual/automatic'------Choose manual adjustment or automatic adjustment;
5、“open/close'------Start and stop trigger the thyristor.
ZK-3C three-phase thyristor voltage regulating trigger
4、 Installation and wiring:
1Dimensions: (Length)*wide*Deep)160*80*130
Installation panel opening size:152*76
2、The wiring terminal is shown in the diagram:

3Connect to four typical control circuits using wiring diagrams (for reference only)

Instructions:1.ZK-3CNo phase sequence requirement for wiring;
2.When placing an order, please specify the form of the control circuit.
5、 Usage of instruments:
1TheZK-3CThe wiring phase sequence requirement is that there are three sets of wires in total. Please distinguish them clearly during use and strictly follow the wiring diagram,
Require all wires to be tightly connected to the thyristor and led out to the instrument.
2Check that all wiring terminals are connected correctly and the power can be turned on. At this point“%'The window is on, and the voltage adjustment indicator light is on
(Or the power adjustment indicator light is on)
3, will“Output regulation'Turn the dial left to the starting point.
4, Press“manual/automatic'Select the output mode button, press the manual output indicator light once, and press the automatic output indicator light again.
5Lightly press“pressure regulation/Adjusting skills'Select the button to trigger the thyristor working mode, which can change the thyristor working mode (at the factory)ZK-3CSet in Adjustment
Press trigger state or set working state according to user requirements.
6Adjust and correct“Output regulation'Dial and observe simultaneously“%'Display window, adjust to the output power you need, and the instrument will enter the trigger mode at the same time
Control the working status of silicon.
7The instrument is set in“pressure regulation'When triggering the thyristor working mode, the output is voltage regulation mode (phase-shifting type).
8Lightly press“close'Key, the instrument stops working.
9The instrument has a power-off automatic shutdown function.
10Built in instrument panel6Digital function switch:
The instrument movement and housing are designed with a plug-in method, and the switch is located behind the display panel. Users can extract the instrument movement according to on-site operating requirements and set it according to the function table.