MITSUBISHI Mitsubishi Electric'sfunction
Uninterruptible Power SupplySummary of MELUPS' Diamond Sink '
Function Overview:
This function synchronizes the phase synchronization target of the UPS with the output bus voltage phase of another system through commands when a bypass power supply failure occurs in the 2N systems of A and B.
When the two system bypass is normal, synchronize with the bypass voltage of each system. Due to the input of the two systems being the same power source, System A and System B are synchronized.
When a bypass fault occurs (voltage, frequency, etc.), this function always synchronizes system A and B by synchronizing with the bus voltage of another system.