Shanghai Xingshen releases new float level transmitter
Date: 2009-02-27Read: 8

electricFloat level transmitterIt is the introduction of FOXBRO technology and original 144LVD by our company. The intelligent level, interface or density measurement transmitter produced by the transmitter component ensures reliable measurement with * degree and stability of the instrument. The transmitter has HART or FOXCOM communication protocol, 4-20mA analog output, and can display%, mA or other physical units for free configuration. The instrument is durable and the sealed electronic component box has moisture-proof and atmospheric pollution resistance performance.

structural principle
LC3144LD typeFloat level transmitterIt consists of a float chamber, a float, a torque tube system, and an electronic measurement system. The float is immersed in the liquid inside the float chamber and is rigidly connected to the torsion tube system. The force borne by the torsion tube system is the net weight of the float minus the buoyancy it receives. Under this combined force, the torsion tube twists a certain angle. The change in the position, density, or boundary height of the liquid inside the float chamber causes a change in the buoyancy of the float immersed in the liquid, resulting in a change in the twist angle of the twisted tube. This change is transmitted to the sensor rigidly connected to the torque tube, causing the sensor output voltage to change, which is then amplified by electronic components and converted into a 4-20mA current output.Float level transmitterUsing a microcontroller and related electronic circuits to measure process variables, provide current output, drive LCD display, and provide HART communication capability.

Main technical parameters

Measurement range: 300-3000mm (larger ranges can be customized)
Accuracy: ± 0.5% FS for liquid level measurement, ± 1% FS for boundary measurement
Repeatability: ≤± 0.25% FS
Dead zone: ≤± 0.2% FS
Power supply: 12-30VDC
Output signal: Analog quantity: 4-20mADC
Digital quantity: according to HART or FOXCOM communication protocol, fieldbus FF communication protocol
LCD display: analog mA or liquid level, boundary and percentage range
Load resistance: 700 Ω (when powered by 24VDC)
Density range: 100<ρ<2000 kg/m3
Zui small density difference: 0.05 g/cm3
Work pressure: 2.5-32.0MPa
Medium temperature: -196 to+400 ℃
Environmental temperature: -40 to+70 ℃
The impact of working conditions:
Power supply impact: When the voltage changes between the minimum and maximum values of the specified voltage, the output change is ≤± 0.2% FS
Temperature influence: ≤ 0.1%/10 ℃
Alarm current: When the liquid level is below the lower limit of the transmitter range by 10% or above the upper limit of the transmitter range by 10%, the transmitter outputs a fault alarm current, which is set to 3.8mA or 22.8mA.