E-mail
122811116@qq.com
-
Phone
15532682888,18330662333,15831621559
-
Address
Industrial Zone, Dacheng County, Langfang City, Hebei Province
Tianjin Cable Factory Rubber Cable Factory
122811116@qq.com
15532682888,18330662333,15831621559
Industrial Zone, Dacheng County, Langfang City, Hebei Province
1140V cable MYP-3 * 25+1 * 16M2 quotation
Mobile flexible cables with rated voltage of 0.66/1.14KV and below
Execution standard: MT818.5-1999
Purpose: This product is a series of mining rubber sheathed flexible cables
Suitable for connecting power lines to mobile coal mining units and other equipment with rated voltage of 0.66/1.14KV and below.
Working conditions:
The rated voltage Uo/U is 0.38/0.66 and 0.66/1.14KV
The long-term operating temperature of cable conductors is 65 ℃
The small bending radius of the cable is 6 times the diameter of the cable
Model name and purpose
MY-0.38/0.66 Mobile rubber sheathed flexible cable for coal mines
Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV
MYE-0.38/0.66 Mobile Elastic Flexible Cable for Coal Mines
Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV
MYP-0.38/0.66 Mobile Shielded Rubber Jacketed Flexible Cable for Coal Mines
Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV
MYPE-0.38/0.66 Mobile Shielded Elastic Flexible Cable for Coal Mines
Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV
MYP-0.66/1.14 Mobile shielded rubber sheathed flexible cable for coal mines
Power connection for various underground mobile coal mining equipment with a rated voltage of 0.66/1.44KV
MYPE-0.66/1.14 Mobile Shielded Elastic Flexible Cable for Coal Mines
Power connection for various underground mobile coal mining equipment with a rated voltage of 0.66/1.44KV
Other requirements and test methods shall be executed in accordance with the MT818.5-1999 standard
The insulation resistance between the main cores of cable insulation and between the main cores and the ground wire shall not be less than 100M Ω· km when converted to+20 ℃.
The transition resistance of the main core shielding layer shall not exceed 3k Ω when converted to 20 ℃.
1140V cable MYP-3 * 25+1 * 16M2 quotationAs the main carrier of power transmission, wires and cables are widely used in electrical equipment, lighting circuits, household appliances, and other fields. Consumers should pay attention to the following points when choosing wires and cables:
1、 It is recommended to purchase products produced by companies that have strict quality control over their own products and have a certain guarantee of product quality.
2、 Pay attention to the product labeling. When purchasing wire and cable products, it is necessary to observe whether the product's certificate of conformity indicates complete information such as product model, specifications, rated voltage, number of cores, production date, implementation standards, license number, etc. The surface of the actual product should be printed with the continuity mark of the factory name, product model, and rated voltage, and verify whether the relevant information between the two is correct.
3、 Check the material of the product. When purchasing cables, pay attention to identifying the material of the cable, such as whether the insulation and sheath are elastic, whether there are burrs or protrusions on the surface, and whether the appearance should be smooth, round, and uniform in color; Whether the copper (aluminum) core can meet the requirements, and if conditions permit, the conductor resistance should be tested.
4、 Pay attention to the length. There is a length label on the certificate of conformity. You can first estimate the length of one round of wire in the finished product packaging, and then count the number of turns in the reel to see if the length of the wire is "short of weight".
5、 When selecting wire and cable products, experienced professional electricians should be consulted to choose wires with appropriate cross-sectional sizes and voltage levels according to their own electrical loads.
In the mine power supply system, armored cables are generally used for high-voltage power supply lines, and their failure rate is much lower than that of rubber sheathed cables used for low-voltage power supply. The power supply in mining areas is a weak link in the power supply system, and the working environment is poor. Therefore, how to choose the type and cross-section of cables is related to the safety of power supply operation. The following introduces the selection of cables and the method of selecting cable cross-sections.
The selection of cable models is closely related to the reliability, safety, and economic feasibility of power supply. Article 400 of the Coal Mine Safety Regulations
1> The level difference of the actual cable laying location should be compatible with the allowable cable laying level difference specified.
2> The cable should have a conductor of sufficient cross-section for protective grounding.
3> It is strictly prohibited to use aluminum wrapped cables.
4> Flame retardant cables that have passed inspection and obtained safety labels for coal mining products must be selected.
5> The cross-section of the main cable core should meet the requirements of the power supply line load.