The DTS600 wireless multifunctional data monitoring host adopts Lora wireless communication and can receive up to 240 wireless sensor accesses. Equipped with RS485 communication interface and supporting standard Modbus RTU protocol. Parameter settings can be made (alarm parameters, communication address, baud rate, ID code, etc.); Real time data can be read through the upper computer management software to achieve centralized data collection. DTS600 sensor data host LoRa communication two-way RS485






DTS600 sensor data host LoRa communication two-way RS485DTS600 sensor data host LoRa communication two-way RS485
DTS600 wireless multifunctional data monitoring host,adoptLora wireless communication can receive up to 240 wireless sensor accesses.possessRS485communication interface,supportstandardModbus RTU protocol.can be performedParameter settings (alarm parameters)NumberMailing AddressBaud rate、ID codeWait;can pass throughThe upper computer management software canrealRead data in real-time to achieve centralizationdata collection.
Key Function Description
Menu Key: Used for confirmation(Note:long pressEnter the system settings interface within 3 seconds.
Up key: parameter addition(Note: InsystemSet interface, press this key to exit the interface.
Down key: Subtract parameters.
Shift key: Select function (note: In the alarm status interface, press this key to switch, long press for 5 seconds after the alarm to mute)
Register type description
The starting address is0x0110 (272 in decimal), each set of data consists of 3 words, in order of data type
valid data1valid data2,The data types of the company's existing products are as follows:
01 represents temperature type, where data 1 (divided by 10) is the temperature value and data 2 is an invalid value-9999(0xD8F1);
02 represents the temperature values of two channels, data 1 and data 2 are the temperature values of the first and second channels respectively, as above
03 represents the temperature and humidity type, where data 1 (calculated by dividing by 10) is the temperature value and data 2 (calculated by dividing by 10) is the humidity value;
*04 represents voltage type, reserved
05 represents the current type,Namely, data1 isCurrent value (unit)0.01A)data2 forinvalid value-9999(0xD8F1);
*Data 2 can also be extended to NTC sensors
06 represents the switch type, where data 1 is the switch value and 0 isdisconnect,1 is closed, data 2 is an invalid value-9999(0xD8F1);
07 represents water immersion type, that is, when the value of data 1 is 1, there is water, when it is 0, there is no water, and data 2 isReference resistance value (unit)K Euro;
*08-11 Reserved
*12expressTilt angle sensor, i.e. data1 is the X-axis inclination angle, and data 2 is the Y-axis inclination angle, ranging from -90.0 to 90.0;
13expresspiezoelectricVibration temperature type, i.e. data1 is the vibration value(Reference Range)0-16000)data2 is the temperature value;
*14expressMEMSVibration temperature type, i.e. data1 is vibrationPeak acceleration(0-16000mg)data2 is the temperature value;
15 represents the vibration (intensity) velocity, that is, data 1 is the vibration velocity value (0.00-50.00mm/s),data2 is the temperature value;
*19 represents the illuminance, that is, data 1 is the illuminance value (0-65535 lux),data2 is the temperature value;
Reserve 20-90
91 represents the pressure temperature type, where data 1 represents the pressure value (unit: 0.001Mpa) and data 2 represents the temperature value
95 represents a 4-20mA standard signal, with data 1 and data 2 representing current values of 4000-20000 (in 0.001mA)