DXN high-voltage live display device

NegotiableUpdate on 11/05
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Overview: The ER-DXN series high-voltage live display device is designed by our company for indoor high-voltage electrical equipment of rated voltage 3-35kV systems

Product Details

Overview
The ER-DXN series high-voltage live display device is designed by our company for indoor high-voltage electrical equipment of rated voltage 3-35kV systems. Not only does it have high-voltage live display and locking functions, but it also has self checking function, which can detect the performance of the device itself, greatly improving the reliability of the device.
This device can be used in conjunction with the electromagnetic lock on the switchgear to implement forced locking and prevent accidental entry into the live compartment, thereby improving the safety performance of the supporting products.

Model Description

technical indicators

Environmental temperature: -10 ℃~85 ℃, relative humidity: ≤ 95% RH;
Rated voltage of the system: 3-35kV;
LED startup voltage (kV): bus voltage x 0.15;
Locking start control voltage (kV): bus voltage x 0.65;
High voltage live sensor:
Power frequency withstand voltage: 30kV, 42kV, 95kV;
Lightning impulse withstand voltage (peak): 60kV, 75kV, 200kV;
Maximum operating voltage: 7.2kV, 12kV, 40.5kV.

Self-check function
The UA, UB, UC, and UN (terminals 13-16) of the device are not connected to voltage and only connected to the working power supply (terminals 9, 10, and 11). Press and hold the self-test button“”The A, B, and C three-phase indicator lights are on, indicating that the device self-test is complete and working normally.

Sensor specifications:
 
serial number Sensor Specifications height
(mm)
maximum diameter
(mm)
creepage distance
(mm)
bending strength
(N)
1

CG3-10Q/130B

130 95 230 8000
2

CG3-10Q/145B

145 95 240 8000
3

CG3-35Q/340

340 172 780 8000
4

CG3-35Q/380

380 172 800 8000

Size and Terminal Definition:



Notes:
·The input terminals of UA, UB, UC, and UN must be connected to the high-voltage bus through dedicated high-voltage live sensors, and must not be connected to high voltage in any other way, otherwise it will cause device damage and inconvenience to your use;
·Connect the wires with a shielding layer and reliably ground the shielding layer;
·2kV/1-minute power frequency withstand voltage test is prohibited between UA, UB, UC and ground;

Power frequency withstand voltage test: 1) Connect the power input terminal in parallel to ground; 2) Connect the output contacts in parallel to ground.

Lock circuit output control logic:
serial number Three phase input voltage Live indicator light status power supply
indicator light
latch
indicator light
relay output
Contact status
Press the self-test button
1

0 (all three phases)

extinguish extinguish extinguish K1 closed
K2 disconnected
2

0 (all three phases)

Bright (all three phases)

bright extinguish K1 disconnected
K2 closed
3

≥ 40V (any phase)

Bright (all three phases)

bright bright K1 closed
K2 disconnected
4

≥ 40V (any phase)

Bright (charged phase)

extinguish extinguish K1 closed
K2 disconnected

Ordering Notice:
·Working power supply: □ AC 85-265V □ DC 110/220V
·System voltage: □ 6kV □ 10kV □ 35kV □ Other
·Device model: ER-DXN □ A prompt type □ B locking type
·High voltage live sensor: □ Use the high-voltage live sensor provided by our company
Note: Due to continuous technological updates, if there are any changes in product specifications and configurations, please refer to the actual supply.