FIP (FLS) graphite or platinum online conductivity electrode sensor probe C150; C200
Product Details

Product Introduction

FIP (FLS)C150-200Conductivity sensors use graphite or high-resolution platinum ring technology. Durable epoxy resin body structureapproveEnsure the robustness and reliability of the sensor. Utilizing the built-in temperature sensor(Pt100)And the monitor/The transmitter'sATC(Automatic temperature compensation) function, these sensors provide accurate high-resolution measurement results. They can be used for laboratory and industrial applications. The sensor electrodes are well protected, so the conductivity cell constant is not easily damaged by solids. According to the required operating range, three conductivity cell constants can be provided. The use of a simple and reusable filler cap allows for cost-effective online installation of electrodes, while the one equipped with an extension tubeof3/4The joint is sufficient for immersiontypeInstallation. useinstallThe kit can install these probes onFIPTType of pipe fittings andFIPOn the saddle clamp.

application

Chemical concentrate

Food industry

evaporation

Metal Finishing and Mining

textile industry

Pulp and Paper Manufacturing

water treatment

reverse osmosis

Softener regeneration

Deionization

distillation

aquaculture

Agricultural and Fertilization Systems

Main characteristics

Graphite or platinum measurement surface

Suitable for laboratory, industrial or portable applications,

But the liquid needs to be filtered

Online and Immersion Installation

Including temperature sensors

follow0.1 - 10The conductivity cell constant option

technical data

general rule

Scope of operation:

- C150.01 TC, C200.01 TC:0.1 µS/cmto2000 µS/cm(10 MΩ*cmto500 Ω*cm)

- C150.1 TC, C200.1 TC:1 µS/cmto20000 µS/cm

- C200.10 TC:10 µS/cmto200000 µS/cm

Temperature compensation equipment(TCMode):Pt100

Cable length:5rice(16 ft.)

Electrode distance controller (no signal adjustment):20rice(66 ft)

Process connection:

-Online installation:

Thread Jointperhaps¾”

FLSInstall accessories

Immersion installation

Working temperature:0°C - 70°C32°F - 158°F

working pressure:7 bar (100 psi)

Welding materials:

-Body: Epoxy resin

-Measurement surface: graphite(C150Edition) or Platinum(C200Version)

FIP (FLS) C150-200Graphite or platinum conductivity sensor probemodel: C150.01; C150.1; C150.01TC; C150.1TC; C200.01; C200.1; C200.10; C200.01TC; C200.1TC; C200.10TC