flame retardant cableWL-ZR-YJGE WL-ZR-YJE
purpose:
flame retardant cableWL-ZR-YJGE WL-ZR-YJEMainly used for35kVFor the purpose of transmitting electrical energy in the following power transmission and distribution systems. Widely used in power, construction, industrial and mining, metallurgy, petrochemicals, transportation and other sectors, it has replaced oil impregnated paper insulated power cables and partially replaced polyvinyl chloride insulated power cables.
Model Description |
1. Flame retardant properties 2. Insulation series code 3. Conductor 4. Sheath 5. Armor layer code |
6. Outer protective layer code 7, rated voltage 8, number of cores 9, conductor cross-section mm2 |
Model code table
project |
code name |
meaning |
Flame retardant properties |
ZR |
Non flame retardant (omitted) |
WL |
flame retardant * |
|
low smoke zero halogen |
||
insulation |
YJ |
Cross linked polyethylene insulation |
Cross linked polyethylene insulation |
- |
Copper core conductor (omitted) |
L |
Aluminum core conductor |
|
Sheath or inner sheath |
V |
polyvinyl chloride |
VD |
Low smoke, low halogen flame retardant polyvinyl chloride |
|
Y |
polyethylene |
|
E |
Flame retardant polyolefin |
|
Armor layer |
2 |
Double layered steel belt armor |
3 |
Fine steel wire armor |
|
4 |
Coarse steel wire armor |
|
outer sheath |
2 |
polyvinyl chloride |
3 |
polyethylene |
|
note*Flame retardant characteristics are divided into three levels: ABC, represented as ZRA, ZRB, ZRC | ||
Model Name Comparison Table
model |
Product Name |
WL-ZR-YJGE |
Copper core cross-linked polyethylene insulated polyolefin sheathed low smoke halogen-free high flame retardant power cable |
WL-ZR-YJGE23 |
Copper core cross-linked polyethylene insulated polyolefin sheathed steel tape armored low smoke halogen-free high flame retardant power cable |
WL-ZR-YJGE32 |
Copper core cross-linked polyethylene insulated polyolefin sheathed fine steel wire armored low smoke halogen-free high flame retardant power cable |
ZR-YJV |
Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed power cable |
ZR-YJV22 |
Copper core cross-linked polyethylene insulated PVC sheathed steel tape armored power cable |
ZR-YJV32 |
Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed fine steel wire armored power cable |
DL-ZR-YJV |
Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed low smoke, low halogen flame-retardant power cable |
DL-ZR-YJV22 |
Copper core cross-linked polyethylene insulated PVC sheathed steel tape armored low smoke and low halogen flame-retardant power cable |
DL-ZR-YJV32 |
Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed fine steel wire armored low smoke and low halogen flame-retardant power cable |
WL-ZR-YJE |
Copper core cross-linked polyethylene insulated polyolefin sheathed low smoke halogen-free flame-retardant power cable |
WL-ZR-YJE23 |
Copper core cross-linked polyethylene insulated polyolefin sheathed steel tape armored low smoke halogen-free flame-retardant power cable |
WL-ZR-YJE32 |
Copper core cross-linked polyethylene insulated polyolefin sheathed fine steel wire armored low smoke halogen-free flame-retardant power cable |
flame retardant cableWL-ZR-YJGE WL-ZR-YJEUse features
itemeye |
technical performance |
rated voltage |
Voltage levels are divided into:0.6/1kV、1.8/3kV、3.6/6kV |
6/6kV、6/10kV、8.7/10kV、8.7/15kV | |
12/20kV、21/35kV、26/35kV | |
Long term allowable operating temperature for conductors |
The working temperature of the conductor is90℃ |
DC resistance |
comply withThe provisions of GB3956 |
lay |
When laying, the ambient temperature should not be lower thanAt 0 ℃, the small bending radius should not be less than 15 times the outer diameter of the cable. |
Power frequency withstand voltage test |
Cables with Uo of 3.6kV and below: 2.5Uo+2kV/5min no breakdown |
Cable with Uo above 3.6kV: 2.5Uo/5min without breakdown | |
Partial discharge test |
When Uo is 1.8kV or above and below 18kV, |
The discharge power of 1.5Uo shall not exceed 20pC; | |
Uo is above 18kV, | |
The discharge power of 1.5Uo should not exceed 10pC. | |
Flame retardant properties |
Can withstand itThe bundled combustion test specified in GB12666.5 (IEC332-3); The smoke concentration during the combustion of low smoke, low halogen, and low smoke halogen-free flame-retardant cables should comply with the provisions of GB12666.7 (IEC1034). |