560 Baoxiang Road, Jiading District, Shanghai

| Product Name: | Imported gas safety solenoid valve | Product Model: | Buhrer series |
| Driving mode: | electromagnetic | Connection form: | Flange, thread |
| Structural form: | Pilot operated, piston operated | Sealing structure: | piston-type |
| Pressure range: | 0.6MPa-6.4MPa | Nominal diameter: | DN1-500 |
| Common materials: | WCB, 304, 316, etc | Technical Consultation: |
Imported gas safety solenoid valve-Buhrer brandWorking principle: When the solenoid valve needs to be opened, the solenoid valve coil is first energized, then the protective sleeve on the top of the valve is unscrewed, and the handle is pulled outward with force to open the solenoid valve. Then, the protective sleeve is placed in its original position to protect the handle. When the solenoid valve needs to be closed, the coil instantly loses power and the solenoid valve quickly closes.
Imported gas safety solenoid valveApplication scope:
It is widely used in industrial furnaces, boilers, gas pipelines, gas treatment plants, gas stations, gas leak alarm systems, safety protection systems, fire alarm systems, and other cities or factories to cut off flammable and explosive media; Quickly cut off when potential accidents are discovered, and promptly prevent the occurrence of malignant accidents.
Imported gas safety solenoid valveProduct Features:
When the power consumption of the solenoid valve coil is 10W, the temperature does not exceed 10 ℃, and the coil can be powered on for a long time, the valve remains in a long-term open state. Power outage or quickly close the power valve. After a power outage or shutdown of the valve coil, the valve will not automatically open and must be manually opened upon subsequent power supply; Energy saving; Zero pressure start, zero leakage.
the United StatesBuhrerBrand series of imported solenoid valves: direct acting solenoid valve, step-by-step direct acting solenoid valve, medium and low pressure solenoid valve, high pressure solenoid valve, ultra-high pressure solenoid valve, ultra-high temperature solenoid valve, steam solenoid valve, low temperature solenoid valve, anti-corrosion solenoid valve, submersible solenoid valve, gas solenoid valve, gas quick cut-off solenoid valve, gas safety solenoid valve, vacuum solenoid valve, pulse type solenoid valve, self-protection solenoid valve, two position three-way solenoid valve, solenoid valve with manual function, solenoid valve with signal function, etc.
Imported gas safety solenoid valveMain technical parameters:
| Product Specifications | DN20--DN500 |
| Valve body material: | Cast steel, stainless steel (cast steel bodies cannot be used on corrosive fluids) |
| Pressure range: | 0~0.6MPa |
| Applicable media: | Gas, natural gas, liquefied gas, biogas, methane, and other gases or fuels |
| Medium temperature: | -20~+100℃ |
| Protective performance: | Waterproof and Explosion proof (Exd IICT5) |
| Wiring method: | Lead type; Plug in type |
| Power supply voltage: | DC12~127V; AC36~380V |
| Connection method: | Pipe connection, flange |
Imported gas safety solenoid valveSpecifications and dimensions:
| Nominal Diameter | L (mm) |
D (mm) |
D1 (mm) |
D2 (mm) |
D3 (MM) |
H (mm) |
flange (Standard) |
L (mm) |
D (mm) |
D1 (mm) |
D2 (mm) |
D3 (mm) |
H (mm) |
flange (Standard) |
|
| DN15 | 100 | Φ65 | 4-Φ14 | Φ46 | Φ89 | 170 | 4.0Mpa | ||||||||
| DN20 | 110 | Φ75 | 4-Φ14 | Φ56 | Φ99 | 185 | 130 | Φ85 | 4-Φ14 | Φ65 | Φ110 | 190 | 4.0Mpa | ||
| DN25 | 125 | Φ85 | 4-Φ14 | Φ65 | Φ110 | 190 | 130 | Φ85 | 4-Φ14 | Φ65 | Φ110 | 190 | |||
| DN32 | 140 | Φ100 | 4-Φ18 | Φ76 | Φ137 | 200 | 150 | Φ100 | 4-Φ17 | Φ76 | Φ135 | 215 | |||
| DN40 | 150 | Φ110 | 4-Φ16 | Φ85 | Φ144 | 215 | 157 | Φ110 | 4-Φ17 | Φ85 | Φ145 | 230 | |||
| DN50 | 155 | Φ125 | 4-Φ16 | Φ100 | Φ152 | 225 | 175 | Φ125 | 4-Φ17 | Φ100 | Φ155 | 240 | |||
| DN65 | 200 | Φ145 | 4-Φ18 | Φ118 | Φ179 | 240 | 1.6Mpa | 235 | Φ145 | 4-Φ17 | Φ120 | Φ180 | 255 | 1.6Mpa | |
| DN80 | 240 | Φ160 | 8-Φ18 | Φ132 | Φ194 | 265 | 270 | Φ160 | 8-Φ17 | Φ135 | Φ195 | 265 | |||
| DN100 | 280 | Φ180 | 8-Φ18 | Φ156 | Φ223 | 285 | 300 | Φ180 | 8-Φ17 | Φ155 | Φ215 | 285 | |||
| DN125 | 325 | Φ210 | 8-Φ18 | Φ184 | Φ248 | 305 | 380 | Φ210 | 8-Φ18 | Φ185 | Φ245 | 305 | |||
| DN150 | 460 | Φ240 | 8-Φ22 | Φ211 | Φ280 | 390 | 440 | Φ240 | 8-Φ22 | Φ210 | Φ280 | 345 | |||
| DN200 | 490 | Φ295 | 12-Φ22 | Φ266 | Φ340 | 440 | 580 | Φ295 | 8-Φ22 | Φ265 | Φ335 | 385 | 1.0Mpa | ||
| Valve body material | stainless steel | cast iron | |||||||||||||
| Applicable pressure | 0~0.6MPa | ||||||||||||||