1: Product Introduction
IDG100-TSP Industrial Dust Concentration AlarmBy testing the concentration of particulate matter in a designated area and converting it into a standard4~20mA、0~5VorRS485Signal, through standard signal, the instrument can directly communicate withDCS、PLCOr Weilian AnIDG1000DControl the host connection to achieve centralized monitoring and control of particulate matter concentration in the entire area.
IDG100-TSP Industrial Dust Concentration AlarmSupporting customersWLO-MultiCollection software, interface based onQTVisual programming design, clear interface, simple operation, software equipped with data storage and query functions, database based onSQLiteUp to storage capacity2TB. Stored procedures use dynamicDLLLink, customers do not need to install any other work software, just open itWLO-MultiSimply configure the serial port, parameters, and storage time to achieve online connectivityPCmonitor.WLO-MultiWe can provide customers with the concentration changes of dust in a certain area during a certain period of time, helping them obtain regular information.
2、 Product Features:
3、 Application scenarios
Indoor environments such as cinemas, hotels, factories, public service areas, building ventilation control, flour mills, furniture factories, etc
4、 Technical parameters
|
test object |
dust |
||
|
Detection Principle |
Laser scattering |
||
|
Detection range |
0~5、30mg/m3 |
||
|
resolution |
0.01、0.1mg/m3 |
||
|
design standards |
GB/T18883-2002 "Indoor Air Quality Standards" |
||
|
execution standard |
Q/WLA 001-2015 "Enterprise Execution Standard of Shenzhen Weilian'an Technology Co., Ltd |
||
|
Working Voltage |
DC24V±6V |
operating current |
<500mA |
|
Shell material |
aluminum alloy |
display mode |
LCD |
|
Detection method |
Diffusion type |
Installation method |
wall-mounted |
|
detection accuracy |
±5% |
repeatability accuracy |
±5% |
|
response time |
<30S |
linearity |
±2% |
|
zero drift |
*Not exceeding ± 3% F.S/year |
signal output |
RS485, Zigbee, GPRS, 4-20mA output |
|
work pressure |
85~105KPa |
Product Life |
2-5 years |
|
Operating Temperature |
-20-50 ℃ (please consult for special requirements) |
Operating Humidity |
10-95% RH non condensing |
|
Overall dimensions |
160*130*50mm |
Total weight |
500g |
|
Attachment |
Packaging box, instruction manual, certificate of conformity |
||