E-mail
liu56817@126.com
-
Phone
13760205028
-
Address
2601, Nan Guang Jie Jia Building, 3037 Shennan Middle Road, Futian District, Shenzhen
Shenzhen Times Peak Technology Co., Ltd
liu56817@126.com
13760205028
2601, Nan Guang Jie Jia Building, 3037 Shennan Middle Road, Futian District, Shenzhen
MI2124 Universal Precision Grounding Resistance Tester——A major breakthrough in grounding resistance testing
In recent years, many users in China have used clamp type resistance meters to measure grounding resistance, but the test results differ greatly from reality. Because the clamp type resistance meter measures the circuit resistance, in some special cases the measurement result may be close to the true value, while in most cases the measurement result is not correct. For example, in the case of a tower with four grounding down conductors, using a clamp type ground resistance meter to test the result shows that the circuit resistance composed of the four grounding down conductors is not the grounding resistance at all. Although the majority of power workers are aware that the test results are inaccurate, they have to adopt this method because it does not require opening the grounding wire and on-site testing is very convenient. Today, a new grounding resistance testing method - the electrode selection method - has been born. This method can accurately measure grounding resistance without disconnecting the grounding wire. It also has the advantages of accurate traditional grounding pile method and convenient clamp method. For grounding resistance testing, choosing the electrode method is of epoch-making significance. To learn more about this method, please request the book "Electrical Testing Theory" from our company. We are pleased to introduce the MI2124 grounding resistance tester, which has the function of selecting electrode method for testing, to our users.
MI2124 Universal Precision Grounding Resistance Tester
It includes three measurement methods:
1: Standard four wire method: The traditional grounding pile method is used to measure the grounding resistance, and the two, three, and four wire methods can be used for measurement,
Can calculate soil resistivity.
2: Double clamp method: No need for pile driving, quick measurement.
3: Electrode selection method: For parallel grounding wires, the grounding of the wire can be accurately measured without disconnecting it
Ground resistance.
MI2124 Universal Precision Grounding Resistance TesterFunction:
-2, 3, and 4 pole method for testing grounding resistance
-Select electrode method to test grounding resistance
-Double clamp method for testing grounding resistance
-Soil resistivity testing function
-Current (effective value) testing function
MI2124 Universal Precision Grounding Resistance TesterCharacteristics and advantages:
-The instrument has strong anti-interference performance and digital signal processing capability. When encountering interference and unstable big data, the digital filter can be turned on
-The input impedance is high. For areas such as concrete floors where ground stakes cannot be driven, steel drills can be directly placed on the ground and then replaced with water or a large wet towel can be placed
-Over limit or incorrect test condition alarm
-1000 test storage and analysis software
-Rechargeable battery power supply, automatic shutdown function
Technical Specifications:
Grounding resistance (four wire method)
-Range: 0-19.99K Ω
-Resolution: 0.01; 0.1; 1;10Ω
-Accuracy:+(2%+3 digits)
-Test voltage:<40V 125HZ
-Short circuit test current:<20mA
-High anti-interference ability: possessing
-Electrode voltage/current testing: with
Grounding resistance (four wire method+clamp grounding test)
-Range: 0-1.99K Ω
-Other parameters are the same as those tested using the four line method
Grounding Resistance Test (Double Clamp Grounding Resistance Test)
-Range: 0--19.99 Ω 20--100 Ω
-Accuracy:+(10%+2 bits)
Soil resistivity:
-Range: 0-1999k Ω m
-Calculation: ρ=2 л aRe
-Electrode distance: 0-30m
-Other parameters are the same as the four lines
Current testing
-Scope: 0-20A
-Resolution: 0.1; 1mA;0.01; 0.1; 1A
- 精度:+(5%+5 位)5 mA---20A
Other parameters:
-Power supply: 4 × 1.5V
-Record: 1000 data points
-Protection level: IP54
-Insulation protection: double insulation
-Computer interface: RS232
-Size: 90x160x180mm, 1.2kg
Ordering Guide
Standard configuration:
-Host
-4.5-meter black and green test wires
-15 meter red test wire
-20 meter blue test wire
-4 grounding piles
-Two 50mm grounding resistance test pliers
-User Manual
-Verification report