Mining mobile cable 3 * 6+1 * 6-MY mining cable 380V

NegotiableUpdate on 11/19
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Mining Mobile Cable 3 * 6+1 * 6-MY Mining Cable 380V $r $n Rated Voltage 0.38/0.66KV Power Connection for Various Underground Mobile Mining Equipment

Product Details

Mining mobile cable 3 * 6+1 * 6-MY mining cable 380V

Mobile flexible cables with rated voltage of 0.66/1.14KV and below

Execution standard: MT818.5-1999

Purpose: This product is a series of mining rubber sheathed flexible cables

Suitable for connecting power lines to mobile coal mining units and other equipment with rated voltage of 0.66/1.14KV and below.

Working conditions:

The rated voltage Uo/U is 0.38/0.66 and 0.66/1.14KV

The long-term operating temperature of cable conductors is 65 ℃

The bending radius of the cable is 6 times the diameter of the cable

Mining mobile cable 3 * 6+1 * 6-MY mining cable 380V

The MYP cable consists of three main cores with insulation shielding and a ground wire wrapped in a semi conductive rubber layer, which is twisted around the semi conductive rubber layer to form a cable.

It is safer to squeeze black chlorinated polyethylene rubber sheath or thick black chloroprene rubber sheath outside.

Conductive core: Made of soft copper wire, its performance complies with GB/T3956-1997.

Insulation: XJ-00A rubber according to GB7594.2-1987 is used.

Core identification: Insulation color separation identification is used, with the main core being red, green, and white.

Ground wire: covered with a semi conductive rubber.

Insulation shielding: Cover the insulation surface with a semi conductive tape.

Cabling: Three main cores and one ground wire are twisted in the right direction around a semi conductive rubber pad core to form a cable.

Sheath: XH-03A rubber according to GB7594.7-1987 is used. The oxygen index of the sheath rubber is ≥ 40.

The flame retardant performance of the finished cable meets the requirements of MT386-1995.

Cable marking: The surface of the cable is printed with the model, voltage, specifications, and manufacturer


Number of cores * Conductor

 

Nominal thickness of sheath (mm)

outer diameter of cable

Reference weight of cable (kg/km)

Nominal cross-section (mm2)

power core

UC-0.38/0.66

UCP-0.38/0.66


power core

Ground wire core

Insulation nominal thickness (mm)

Small value

Large value

Small value

Large value

UC

UCP




3*4

1*4

1.4

3.5

20.3

23.4

23.7

27.2

670

785



3*6

1*6

1.4

3.5

23

26.4

26.4

30.1

838

927



3*10

1*10

1.6

4

27.5

31.3

30.9

34.7

1292

1400



3*16

1*10

1.6

4

29.6

33.4

33

36.8

1465

1586



3*25

1*16

1.8

4.5

35.6

39.8

39

43.2

2159

2296



3*35

1*16

1.8

4.5

38.7

42.1

42.1

46.3

2596

2783



3*50

1*16

2

5

43.6

47.1

47.1

51.4

3385

3548



3*70

1*25

2

5

49.7

54.4

52.4

57.1

4292

4477




Model name and purpose

MY-0.38/0.66 Mobile rubber sheathed flexible cable for coal mines

Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV

MYE-0.38/0.66 Mobile Elastic Flexible Cable for Coal Mines

Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV

MYP-0.38/0.66 Mobile Shielded Rubber Jacketed Flexible Cable for Coal Mines

Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV

MYPE-0.38/0.66 Mobile Shielded Elastic Flexible Cable for Coal Mines

Power connection of various underground mobile coal mining equipment with rated voltage of 0.38/0.66KV

MYP-0.66/1.14 Mobile shielded rubber sheathed flexible cable for coal mines

Power connection for various underground mobile coal mining equipment with a rated voltage of 0.66/1.44KV

MYPE-0.66/1.14 Mobile Shielded Elastic Flexible Cable for Coal Mines

Power connection for various underground mobile coal mining equipment with a rated voltage of 0.66/1.44KV

Other requirements and test methods shall be executed in accordance with the MT818.5-1999 standard

The insulation resistance between the main cores of cable insulation and between the main cores and the ground wire shall not be less than 100M Ω· km when converted to+20 ℃.

The transition resistance of the main core shielding layer shall not exceed 3k Ω when converted to 20 ℃.